10 installation

guide

",!#+

7()4%

",!#+

",!#+

",!#+

7()4%

'2%%.

electrical installation/high voltage wiring

MODEL

VOLTS

AMPS

WIRE SIZE / DISTANCE IN FEET

12 AWG

10 AWG

8 AWG

6 AWG

1601/1603

120

5.4

170

275

460

685

1601/1603

230

2.7

685

1100

1830

2750

1601/1603

460

1.35

2875

4600

7665

11500

The distance shown in the chart is measured in feet from the operator to the power source.

If power wiring is greater than the maximum distance shown, it is recommended that a

service feeder be installed. When large gauge wire is used, a separate junction box must

be installed for the operator connection. The wire table is based on stranded copper wire.

Wire run calculations are based on a 3% voltage drop on the power line, plus an additional

10% reduction in distance to allow for other losses in the system.

Connect the High-Voltage wiring to the
terminal block as shown.

2

All wiring must comply with local code requirements.
To protect against surges and power fl uctuations it is recommended that a surge suppresser be installed on
the high voltage power lines
For 230 and 460 Volt 3-phase input power, use only two legs of the incoming 3-phase power.

From the High-Voltage conduit, route the
wiring cable up to the terminal block.

1

1

2