Electrical installation/ timer down application – Controlled Products Systems Group 1601-080 User Manual

Page 19

background image

1601-065-M-05-07

20 installation

guide

electrical installation/timer down application

1 2 3 4 5 6 7 8 9

10 11 12 13 14

SW2

7

8

3- DATA OUT
2- DATA IN
1- COMMON

TB 2

TB 1

DOWN

PORT

9409

Loop

Detector

!CCESS

#ONTROL

$EVICE

COM

N.O.

!RMING

/PTIONAL

2EVERSE

2EVERSE

1

2

3

4

5

6

7

8

ON

OFF

SW1

3PEED

Spacing of the loops is critical when using this configuration. Be sure that the loops are spaced as shown in the diagram.

1

2

3

4

5

Use a 9405 loop detector plugged into the DOWN port on the 1601 circuit board. Connect the REVERSE loops, wired in series, to
terminals TB-1 and the ARMING loop to terminals TB-2.

If the optional arming loop is not used, use a 9406 detector plugged into the DOWN port on the 1601 circuit board and connect

the REVERSE loops, wired in series, to terminals TB-1 on this detector.

The timer (SW-1, switch 7) should be ON. The arm will rotate down after the vehicle clears the reverse loops and the timer

times out.

SW-1, switch 4 must be OFF.

1

2

3

4

5