beautypg.com

Model cmf series 7.8.2 list of error numbers – Fluid Components International CMF Series Manual Electronics Setup and Menus User Manual

Page 23

background image

Commissioning

Fluid Components Intl

Document 06EN003327 Rev. -

73

FlexCOR

Model CMF Series

7.8.2 List of error

numbers

Error Error text

#Comment

Outputs

Input

No.

Remedy text

status

status

1

I1 - Power on
OK

Power on has activated

Active

Active

2

I2 - Add-on Module
Applied

A new module has been added to the system

Active

Active

3

I3 - Add-on Module

An add-on module is defective or has been removed.

Install

This can also be an internal add-on module

Active

Active

4

I4 - Param. corrected

A less vital parameter in the converter has been

OK

replaced by its default value

Active

Active

20

W20 - Totalizer 1

During initialization the check of the saved totalizer

Reset manually

value has failed. It is not possible to rely on the
saved totalizer value. The totalizer value must be
reset manually in order to rely on future readings

Active

Active

20

W20 - Totalizer 2

During initialization the check of the saved totalizer

Reset manually

value has failed. It is not possible to rely on the
saved totalizer. The totalizer value must be reset
manually in order to rely on future readings

Active

Active

21

W21 - Pulse overflow

Actual flow is too big compared with pulse width and

Reduced

Adjust pulse settings

mass/pulse

pulse width

Active

22

W22 - Batch timeout

Duration of batching has exceeded a predefined

Batch out-

Check installation

max. time

put on zero

Active

23

W23 - Batch overrun

Batch quantity has exceeded a predefined maximum

Batch out-

Check installation

overrun mass or volume

put on zero

Active

24

W24 - Batch neg. flow
Check flow direction

Negative flow direction during batch

Active

Active

30

W30 - Flowsaturated
Adjust max. flow

Flow is above Q

max.

settings

Max. 120 %

Active

31

W31- Empty pipe

Pipe is empty

Zero

Active

32

W32 - Temp. to high

The temperature of the fluid has exceeded the max.

Adjust temperature

temperature rating of the sensor (180 °C)

Active

Active

33

W33 - Temp. to low

The temperature of the fluid has exceeded the min.

Adjust temperature

temperature rating of the sensor (-50 °C)

Active

Active

34

W34 - Zero Adj. fail

The zero-point adjustment values are outside the limit

Check flow = zero

because there is not zero flow in the sensor. Check
zeroflow conditions, valves, pumps etc.

Active

Active

35

W35 - Current Out 1

Current output exceeds 120%. Ensure that the sensor is

Check max. settings

correctly sized and check max. flow setting

Active

Active

36

W36 - Freq/Pulse Out1

Freq/Pulse output exceeds 120%. Ensure that the sensor

Check max. settings

is correctly sized and check max. flow setting

Active

Active

40

P40 - SENSORPROM

®

Insert

SENSORPROM

®

unit not installed

Active

Active

41

P41 - Parameter range

A parameter is out of range.

Switch off and on

The error will disappear at the next power-on

Active

Active

42

P42 - Current output

Current loop is disconnected or the loop resistance

Check cables

is too big

Active

Active

43

P43 - Internal error

Internal error

Switch off and on

Active

Active

49

P49 - Protec. viol.

Too many errors occured at the same time.

Switch off and on

Some errors are not detected correctly

Active

Active

50

P50 - Temp. cable

Error in temperature sensor, check cables and

Check cable

connectors

Active

Active

51

P51 - Pick-up 1

Pick-up 1 amplitude too low. Check cables or application

Check cable/install.

for damping (air/gas in liquid)

Active

Active

52

P52 - Pick-up 2

Pick-up 2 amplitude too low. Check cables or application

Check cable/install.

for damping (air/gas in liquid)

Active

Active

60

F60 - CAN comm. error

CAN bus communication error. An add-on module, the

Converter/add-on module

display module or the converter is defective

Zero

Inactive

61

F61 - SENSORPROM

®

err.

It is not possible to rely on the data in SENSORPROM

®

Replace

unit

Active

Active

62

F62 - SENSORPROM

®

ID

The SENSORPROM

®

unit ID do not comply with the

Replace

product ID. The SENSORPROM

®

unit is from another

type of product.

Zero

Inactive

63

F63 - SENSORPROM

®

It is not possible to read from the SENSORPROM

®

Replace

unit

Active

Active

70

F70 - Pick-up phase

Check cables/polarity

Active

Active

71

F71 - Driver phase

Check cables/polarity

Active

Active

80-83

F80, 81, 82, 83 - Internal error Restart or replace

Active

Active

84

F84 - Sensor level

Pick-up amplitud saturated

Active

Active

97

F97 - Add-on module to old

Replace

Active

Active

Error code level:
W = Warning, F = Fatal, P = Permanent