Commissioning
FlexCOR
™
Model CMF Series
60
Fluid Components Intl
Document 06EN003327 Rev. -
7.5.3 External input
7.5.2 Relay output
The output functions error level, error number and direction/limit can also be implemented on the
relay output. Programming of the realy output is identical as is the digital output.
External input menu
The transmitter has one digital input available. If the input is activated with a logic signal
(11 - 30 V d.c.) the meter carries out the activity selected under the menu option. The following
functions can be selected:
Start batch. If the transmitter is used for batching this can be activated automatically by this
function.
Hold/continue is also used in connection with batching and on being activated for the first time
will pause the batch. When activated again it will continue the batch.
Stop batch will stop the batch, i.e. the digital output goes to logic 0. The batch is then reset.
Zero adjust activates the automatic 0-point adjustment.
Reset totalizer can be used to reset internal totalizer 1, 2 or both.
Force output forces all outputs to adopt the value selected in the menu. For example, if 100% is
selected, this means that on activation of external output the current output will show 20 mA and
the frequency output will show 10,000 kHz if set to 0 - 10 kHz.
Freeze input freezes all the current measured values in the display and outputs.
Menu detail