0x200a, Power supply alarm values, Ensor – Burkert Type 8746 User Manual
Page 10: Ktor, Odul description of initiation files eds, 0x200a power supply alarm values

S
ensor
A
ktor
M
odul
Description of initiation files EDS
Description_of_InitiationFilesEDS_2
Version 1.4
page 8 / 27
3) Module’s state and mode
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0 not used
0 not used
Namur mode:
0 – auto
1 – manual
2 - flashing
Namur state:
0 – normal
1 – diagnose active
2 – maintanace required
3 – out of specification
4 – warning
5 - error
4) Module number
0x01
CoreInterface
0x02
BueS
0x03
SubBueS
0x04
MessageDispatcher
0x05
Blackboard
0x06
StorageHandler
0x07
FlashStorageHandler
0x08
EEPromStorageHandler
0x50
Implementation
0x82
InitExit_User
0x83
FlowSensor
0x84
Controller
0x85
PropValve
0x86
Autotune
0x87
DeviceDiagnose
0x200A
Power Supply Alarm Values
sub name
description
ac
ce
ss
type
flags
accesrigths
im
p
o
rt
Im
p
o
rt
d
e
vID
S
IM
-C
a
rd
R
-
u
se
r
W
-
u
se
r
R
-
a
d
v.
u
s
e
r
W
-
a
d
v.
u
se
r
R
-
in
sta
ll
e
r
W
-
ins
ta
lle
r
R
-
b
u
e
rke
rt
W
-
b
u
e
rke
rt
1 Voltage error limit high
A device error will be generated if power supply passes this
value as float32 in volts
RO
- - x - x - x x
2 Voltage error limit low
A device error will be generated if power supply falls below
this value as float32 in volts
RO
- - x - x - x x
3
Voltage warning limit
high
A device warning will be generated if power supply passes
this value as float32 in volts
RW
- - x - x x x x
4
Voltage warning limit
high
A device warning will be generated if power supply falls
below this value as float32 in volts
RW