Maintenance,Troubleshooting

Warning!

for control function i – danger if control pressure fails!
For control function I control and resetting occur pneumatically. If
the pressure fails, no defined position is reached.
• To ensure a controlled restart, first pressurize the device with

control pressure, then switch on the medium.

11.2. Maintenance Work

actuator:
The actuator is maintenance-free provided it is used according to these
operating instructions.

Wearing parts of the angle seat valve / 3/2-way globe valve:
• Seals
• Swivel plate

If leaks occur, replace the particular wearing parts with an appro-
priate spare part (see Chapter “12. Spare parts”).

11.2.1. recommended maintenance

intervals

The valve should be visually inspected once a year. Shorter mainte-
nance intervals are recommended depending on application condi-
tions. The visual inspection includes the pneumatic connections and
the medium connections as well as the deaeration bore in the pipe.

11.2.2. cleaning

Commercially available cleaning agents can be used to clean the
outside.

note!

avoid causing damage with cleaning agents!
• Before cleaning, check that the cleaning agents are compatible

with the body materials and seals.

Follow instructions for use in the Ex area! See chapter “3.1”.

11.3. Malfunctions

malfunction

remedial action

Actuator
does not
switch

Control air connection interchanged

3)

CFA: Connect lower control air connection
CFB: Connect upper control air connection
CFI: Lower control air connection: Open

Upper control air connection: Close

Control pressure too low

See pressure specifications on the type label

Medium pressure too high

See pressure specifications on the type label

Direction of flow interchanged

See direction or arrow on the type label