Carlon Structured Cable Management Systems Handbook - Low Res User Manual
Page 33

31
1
1
/
2
" (SCH4X1C-50), and 2" (SCJ4X1C-50) trade sizes. Pull
tape pre-installed in 1", 1
1
/
4
", 1
1
/
2
", and 2" trade sizes.
B. Fittings for Resi-Gard
®
Flexible Raceway: UL Listed,
orange, Quick Connect
3
/
4
" and 1" Couplings (SCA240E,
SCA240F), Threaded Adapters (SCA243E, SCA243F) or Snap-
In Adapters (SCA253E, SCA253F) and/or 1
1
/
4
", 1
1
/
2
", or 2"
Male Terminal Adapters (SCE943G, SCE943H, SCE943J), or
Standard Couplings (SCE940G, SCE940H, SCE940J).
C. Nonmetallic Outlet and Device Boxes: UL Listed Blue
Boxes manufactured by Carlon.
D. Brackets: UL Listed, orange, Add-On Bracket with (2)
3
/
4
"
flexible raceway connections (SC100SC), UL Listed, orange,
Adjustable Brackets (SC100ADJC, SC200ADJC), or UL Listed,
orange Brackets with (2)
3
/
4
" flexible raceway connections
and (2) pre-installed nails and flange (SC100A, SC200A).
E. Divider Plate: UL Listed, orange partition (SCDIV) used
with Carlon
®
SuperBlue
™
Boxes (BH235A, BH353A,
BH464A, and BH234R).
F. Dual Voltage Box/Bracket: UL Listed, blue with (2)
3
/
4
"
flexible raceway connections and (2) pre-installed nails
(SC200DV).
H. Mud Ring: UL Listed, orange (SCA410).
I. Cable Clips:
1
/
4
" (SC14CC),
1
/
2
" (SC12CC),
3
/
4
" (SC34CC)
orange clips with pre-installed nails.
J. Conduit Clamps: Orange
3
/
4
" (SCE977EC), 1" SCE977FC),
1
1
/
4
" (SCE977GC), 1
1
/
2
" (SCE977HC), and 2" (SCE977JC) sizes.
K. Solvent Cement: Resi-Gard
®
Solvent Cement (VC9963SC).
PART 3. EXECUTION
3.1 Raceway Application
A. Indoor Use Only:
B. Raceway Fittings: Compatible with raceways and suitable
for use and location.
3.2 Installation
A. Keep raceways at least 6 inches (150mm) away from
parallel runs of flues and steam or hot-water pipes.
B. Do not use Resi-Gard in Air Handling Plenums.
C. Maintain separation between power wiring and
telecommunications/fiber-optic cabling.
D. Use proper solvent cement and adhere to safety precautions.
E. Consult Carlon
®
Structured Cable Management Systems
Handbook for more detailed information.
3.3 Protection
A. Maintain conditions that ensure products are without
damage or deterioration at time of Substantial Completion.
3.4 Cleaning
A. After completing installation of exposed, factory-finished
raceways, boxes, and brackets, inspect exposed finishes
and repair damaged finishes.
Gross Automation (877) 268-3700 · www.carlonsales.com · [email protected]