beautypg.com

Carlon E-Loc User Manual

Carlon Equipment

background image

®

INSTALLATION INSTRUCTIONS FOR E-LOC COUPLINGS

1.

Check and make sure sizing of fitting is same as the conduit/innerduct

being installed. E-LOC® couplings are based on standard IPS nominal

outside diameters.

2.

Wipe spigot end of conduit/innerduct clean. Make sure it is clean of burrs,

dirt, or foreign material.

3.

The spigot end of the conduit/innerduct can be lubricated with water or

water with a small amount of liquid dishwashing soap. (Do not use motor

oil or thread lubricants commonly used for metal pipe threads. This

includes W-D 40 “type” lubricant.)

4.

On smaller diameter conduit/innerduct, position fitting on the duct – place

a board across the end and hit with a small mallet or hammer. (Do not hit

the fitting directly with the hammer.) On larger diameter conduit, clean

and lubricate spigot as above. Put a 3” mark on spigots of 4” and larger

conduit/innerduct to make sure the fitting is “home”. Use a bar and block

to push the joint. If a hammer and block of wood are used, make sure

wood is in contact with both sides of the fitting and hit block center. (Do

not hit the fitting directly with the hammer.) Check to be sure that the

fitting is all the way “home” onto the conduit/innerduct.

www.carlonsales.com

5.

When joining conduit/innerduct off a reel, install E-LOC® coupling on the

plain end coming from the reel using steps #1 through #4 above. After the

coupling is installed properly, clean the spigot of the other

conduit/innerduct and push onto spigot end of the conduit/innerduct. If

necessary, place a small board on the edge of the coupling toward the

reel and drive the coupling onto the conduit/innerduct. (Do not hit the

fitting directly with the hammer.)

Gross Automation (877) 268-3700 · www.carlonsales.com · [email protected]