Page 29 of 43
7 Default
Values
Setting
Default Value
STS priority
On-line
Mains high loss volt
138V
Mains low loss volt
100V
Inverter input high loss volt for STS
138V
Inverter input low loss volt for STS
100V
Inverter output high loss volt
138V
Inverter output low loss volt
100V
Inverter shutdown due to low input volt
40V
Inverter shutdown due to high input volt
60V
Inverter output volt
120V
Inverter output volt frequency
60Hz
Inverter output power limit
100%
Table L–120Vac system factory defaults
Setting
Default Value
STS priority
On-line
Mains high loss volt
264V
Mains low loss volt
185V
Inverter input high loss volt for STS
264V
Inverter input low loss volt for STS
185V
Inverter output high loss volt
264V
Inverter output low loss volt
185V
Inverter shutdown due to low input volt
40V
Inverter shutdown due to high input volt
60V
Inverter output volt
230V
Inverter output volt frequency
50Hz
Table M–230Vac system factory defaults
Setting
Default Value
RS-232, RS-422, RS-485 communication baud rate
2400bps
RS-422 address
9999
Button tone
On
LCD brightness value
45
Language English
Password 1234
Dry contact 1
Inverter overload
Dry contact 2
Inverter unavailable
Dry contact 3
Inverter fan fault
Dry contact 4
STS fan fault
Dry contact 5
Inverter power limit
Table N–System parameter factory defaults