beautypg.com

So "table v, Table v — boost/buck/line transfer thresholds – Alpha Technologies FXM 650, 1100, 2000 UPS User Manual

Page 84

background image

017-230-B4 Rev B

82

Table T — Electrical Specifications

Parameter

Value

Battery Charger Current,

Amps

FXM 650: 10

FXM 1100/2000: 15.

Battery Charger Temperature

Compensation

8

-5 mV/°C/Cell (factory default), user adjustable from 0 to -6 mV/°C/Cell in increments of

0.5.

Battery type Anderson Power mating part SB50 or equivalent.

Table U — Regulatory

Parameter

Value

Electrical Safety UL 1778, CSA 107.3, EN 62040-1-2, EN60950-1.

Emission FCC Part 15, Subpart B, Class A, CSPR22, EN55022 Level A.

Marks

C

CSA

US

, CE (230 Vac versions only).

Packaging Designed to meet requirements for ISTA program.

7. Efficiency is measured at an ambient temperature of 25°C, full resistive condition and nominal Line and Battery voltage.

8. With external battery temperature probe assembly. For FXM650-48(Q), charger compensation is disabled.

Table V — Boost/Buck/Line Transfer Thresholds

Parameter

Value

120 VAC Units

230 VAC Units

High Line Transfer

High Line Retransfer

175 VAC

162 VAC

325 VAC

303 VAC

Buck 2 Transfer

Buck 2 Retransfer

152 VAC

146 VAC

282 VAC

272 VAC

Buck 1 Transfer

Buck 1 Retransfer

134 VAC

128 VAC

250 VAC

236 VAC

Boost 1 Retransfer

Boost 1 Transfer

116 VAC

112 VAC

210 VAC

207 VAC

Boost 2 Retransfer

Boost 2 Transfer

102 VAC

98 VAC

180 VAC

176 VAC

Low Line Retransfer

Low Line Transfer

97 VAC

88 VAC

162 VAC

151 VAC