5.3.3 Procedure

1. If used, connect the following ports (see Figure 1 on page 7 for location of numbered elements):

• Ethernet port

4

.

• RS-232 port

7

.

• Dry contacts

9

.

• User inputs

10

.

2. Connect the load to the Alpha FXM Output terminal block

14

. Torque to 1.4 N-m (12 lb-in).

3. Connect the line power to the Alpha FXM AC Input terminal block

13

. Torque to 1.4 N-m (12 lb-in).

4. If needed, attach the terminal block covers and battery harness restraining bracket.

WARNING!

Before proceeding, verify that the line wire is attached to the line terminal block, the

ground wire is attached to the ground terminal block, and the neutral wire is attached to

the neutral terminal block to prevent accidental shocks or electrocutions.

5.4 UATS and (UGTS) Option

The Universal Automatic Transfer Switch (UATS) and Universal Generator Transfer Switch (UGTS) are the next

generation of Automatic Transfer Switch (ATS) and Generator Transfer Switch (GTS) products. They are optional

add-on switching units specifically designed for the FXM UPS family (FXM 650, 1100 and 2000), the Micro UPS

family (Micro 300 and 1000) and the Alpha FXM350/ Micro350 UPS. These switching units provide power and/or

bypass capacity (automatic or manual) so that the operator may safely disconnect the UPS from line or generator

power for easy removal and servicing. In bypass mode, the loads are directly connected to the line or generator

power without any conditioning. Depending on the use of one and/or the other, the UATS/UGTS allows the use

of up to 3 different back-up sources (line, batteries and generator). Refer to the UATS/UGTS Installation Manual

(Alpha P/N 020-165-B0) for details.

WARNING!

Make sure you have read and understood the instructions given in the UATS/UGTS In-

stallation Manual before making any connection to the supply.