Table B — Control Menu

LCD display

Meaning

Description

SENSE TYPE

Sense Type

This function can only be used when the Alpha FXM is in Standby or Shutdown

mode (Table A).

Normal: The Alpha FXM can operate successfully with most line conditions.

OR:

Generator: This setting increases noise tolerance so the fluctuations created by 

a generator are acceptable. (A noisy line can cause the Alpha FXM to constantly

switch between inverter and line modes.)

FUNC MODE

Functional

Mode

The Functional mode can be changed when the Alpha FXM is in any mode (Table C

and "Table V  — Boost/Buck/Line Transfer Thresholds" on page 82).

Automatic Voltage Regulation (AVR): Buck and boost modes are active.

OR:

Quality: Buck and boost modes are switched off; the input voltage is the Alpha FXM

output voltage.

VOLTAGE

Voltage

Sets the Alpha FXM output voltage setting to one of the voltages specified in 

"Specifications" on page 80. Changing the voltage setting from factory default

should  be done by a qualified technician acting under the instructions of Alpha 

Technical Support (1 888 462 7487). Failure to contact Alpha Technologies before

performing this procedure could void your warranty.

AUTO FREQ

Automatic

Frequency

Detection

Enable (default) allows the unit to detect and automatically configure the AC input 

frequency (50Hz or 60Hz).

In cases where the AC input frequency can be out of range for long periods,

Disable prevents the unit from switching back and forth between 50Hz and 60Hz.

FREQUENCY

Frequency

The frequency can only be changed when the Alpha FXM is in Standby mode—to

50 Hz or 60 Hz. This change should ONLY be done by a qualified technician acting 

under the instructions of Alpha Technical Support (1 888 462 7487). Failure to

contact Alpha Technologies before doing this procedure could void your warranty.

QUAL TIME

Line qualify

time

Set how long it takes for the Alpha FXM to return to Line mode after the line has

become requalified to make sure the line is stable. The factory default setting 

is 3 seconds. User adjustable in increments of 1 sec until 1 minute, and then in

increments of 1 minute to 15 minutes max.

INV CUTOFF

Inverter Cutoff

(Enabled/

Disabled)

When

Disable is selected the default FXM inverter cutoff threshold is used.

When

Enable is selected the user configured inverter cutoff threshold voltage is 

used.

INV CUTOFF

Inverter Cutoff

Threshold

(Voltage)

Defines the point where the unit will switch from Inverter to Standby when the 

battery is considered to be low or in order to preserve the battery. See "UPS

Maintenance > Inverter" on page 40.

CHARGER

Battery

charging

options

When

Standard charger is selected, set BATT FLOAT to AUTO or Constant.

When

Bulk charger is selected, set MAX VOLT and FLOAT VOLT. See section 6.2.2

BATT FLOAT

Battery

charging float 

options

When

BATT FLOAT is set to Constant, the default max charge voltage is 54.6V

and float is 54.2V, both at 25°C. Temperature compensation will be active

When

BATT FLOAT is set to AUTO, the float voltage is set to 1.8V below the max 

charge voltage. The default max charge voltage is 54.6V and default float is 52.8V, 

both at 25°C

BATT COMP

Battery

temperature

compensation

Sets the battery temperature compensation to match the batteries you are using. It

can be set from 0 to -6 mV/°C/Cell in increments of 0.5. The factory default setting 

is -5 mV/°C/Cell.

DATE FRMT

Date Format

Selection

Toggles the Alpha FXM date format between YY-MM-DD, MM-DD-YY, DD-MM-YY

YYYY-MM-DD, MM-DD-YYYY, DD-MM-YYYY, YY-TXT-DD, TXT-DD-YY, DD-TXT-

YY, YYYY-TXT-DD, TXT-DD-YYYY, DD-TXT-YYYY, YYYY-DD-TXT, YY-DD-TXT,

YYYY-DD-MM, YY-DD-MM. The factory default setting is MM-DD-YY.

CLOCK FRMT

Clock display

format option

Format to display time information: in 24 hour clock format or 12 hour clock (AM/

PM).

INV RECORD

Inverter record

clear

Clears the inverter counter and timer from the LCD system status menu.

CHGR CUR

Charger current

Charging current can be set to 0A or any value between 2 and maximum in

increments of 1A, where maximum = 15A for FXM1100/FXM2000 and 10A for 

FXM650. (Charging current cannot be set to 1A).

When charging current is set to 0A, the charger will stop charging.