Restoring All Parameters to Default Values

The purpose of this command is to reset the Alpha FXM to the factory default parameters in Table D. Battery

charger related defaults are reset according to the charging method selected at the time the defaults are applied.

Table D — Parameters/ Default Settings

Parameters

Default Settings

Battery charging current (Amps)

10

Temperature compensation of battery charging

(mV/°C/Cell)

Standard charging method: -5.0

Bulk charging method: 0

Maximum charge voltage: Standard > Auto mode @25

°C

(V)

54.6

Maximum float voltage: Standard > Auto mode @25

°C

(V)

52.8

Maximum charge voltage: Standard > Constant mode @25

°C

(V)

54.6

Maximum float voltage: Standard > Constant mode @25

°C

(V)

54.2

Maximum charge voltage: Bulk mode (V)

53.5

Maximum float voltage: Bulk mode (V)

53.5

Default low battery warning Bulk mode (V)

44

Type setting of programmable user input #1

Edge trigger

Level setting of programmable user input #1

Low

Action #1 setting of programmable user input #1

Self test

Action #2 setting of programmable user input #1

None

Type setting of programmable user input #2

Level toggle

Level setting of programmable user input #2

Low

Action #1 setting of programmable user input #2

User alarm on

Action #2 setting of programmable user input #2

User alarm off

Type setting of programmable user input #3

Edge trigger

Level setting of programmable user input #3

Low

Action #1 setting of programmable user input #3

Shutdown on

Action #2 setting of programmable user input #3

Shutdown off

Type setting of programmable user input #4

Edge trigger

Level setting of programmable user input #4

Low

Action #1 setting of programmable user input #4

None

Action #2 setting of programmable user input #4

None

Start hour of rush hour of time of day action period #1

00

Start minute of rush hour of time of day action period #1

00

End hour of rush hour of time of day action period #1

00

End minute of rush hour of time of day action period #1

00

Start hour of rush hour of time of day action period #2

00

Start minute of rush hour of time of day action period #2

00

End hour of rush hour of time of day action period #2

00

CAUTION!

This command resets all parameters that are user-configurable. The command is pass-

word protected. All previously programmed operation will be lost.