6.5.9 Viewing the Serial Number

To display the serial number of the Alpha FXM UPS, type "∗QY0" at the command line and press "Enter".

6.5.10 Setting the Peukert Number and Capacity

You can set the Peukert Number and Capacity using the HyperTerminal interface or the web interface. To display

the current Peukert Number, type "∗QY6" at the command line and press "Enter".

To change the Peukert Number to 1.1345 fro example, type "∗ST6:1.1345" at the command line and press "Enter".

To display the current Peukert Capacity, type "∗QY7" at the command line and press "Enter".

To change the Peukert Capacity to 109.123 for example, type "∗ST7:109.123" at the command line and press

"Enter".

To determine the Peukert number and capacity of your battery, refer to Appendix A.