017-230-B4 Rev B

Controlling the external fan by temperature triggered dry contact

The Temperature trigger has a user configurable range of +20°C to +55°C (68 – 131 °F). When the battery

temperature (monitored by the Battery Temperature Probe) reaches the threshold, the assigned relay closes and

turns on the external fan.

1. Assign the Temperature trigger function to an available dry contact, (for example, c1=11, where 11 is the

assigned index for the Temperature trigger function.)

2. At the HyperTerminal screen prompt, type Temp and press Enter to display the current temperature setting.

For example the Alpha FXM might return *temp=20.

3. To change the value to +35°C, type temp=35 and press Enter. The Alpha FXM returns *temp=35 as

confirmation.

Figure 56 — Temperature trigger function via HyperTerminal

Resetting the Dry Contact Settings

To reset the dry contact settings to the factory default, type default and press Enter. The Alpha FXM responds

with *default, showing it is reset. This command also resets the timer setting to the 2 hours factory default. See

Table S on page 80 for the factory default settings of dry contacts.