Procedure – Alpha Technologies FXM 650, 1100, 2000 UPS User Manual

Page 26

background image

017-230-B4 Rev B

24

6.2.1 The LCD Control Menu

The control menu (Table B) lets you operate the Alpha FXM or program it to suit your operating conditions.

Procedure

1. From the Logo screen go to the Control menu.

2. Press the SELECT button to enter the submenu (Table B).

3. Press the SCROLL button to move between items in the submenu.

4. When you have reached the item you want to change, press the SELECT button. The item chosen is blinking.

5. To toggle between the choices, press the SCROLL button. Stop when you reach the choice you want.

6. To make the change, press the SELECT button. The blinking stops.

Table B — Control Menu

LCD display

Meaning

Description

INVERTER

Inverter

(Enabled/ 

Disabled)

When

Disable is selected and AC is lost, the FXM will be in Standby mode. The

inverter cannot be started through the Inverter On/Off menu, 

When

Enable is selected and AC is lost, the FXM will be in Inverter mode. Turning

inverter on/off manually will work.

INVERTER

Inverter (On/

Off)

When inverter mode is set to ON, the Alpha FXM provides backup battery power

to the load. This mode of operation is normally activated automatically when line

power becomes unavailable, or the line power is not qualified. You can also put 

the Alpha FXM into this mode during initial startup in the absence of line power or

because of unqualified line power. 

LVD DSCNNCT

Battery voltage value at which the LVD configured relay should open

LVD CONNECT

Battery voltage value at which the LVD configured relay should close

BYPASS

Inverter Bypass

This function can only be switched on when the Alpha FXM is in Line mode. When

switched on, it locks the Alpha FXM into the Line mode, switches off the battery

charger and makes the output voltage equal to the input voltage.

Used when:

• 

Replacing the batteries.

OR:

• 

To allow the use of a break-before-make manual bypass switch so the

Alpha FXM can be shut off for maintenance or replacement without interrupting

power to the load.

BATT TEST

Battery Test

Available when

CHARGER on the Control Menu is set to Standard method.

Starts the battery test, which uses depth-of-discharge setting, the battery capacity,

Peukert number, and open-circuit voltage. This setting can be adjusted using

BT TS

DOD menu. A battery test is also performed during the self test.

BT TS DOD

Battery Test

Depth-of-

Discharge

Available when

CHARGER on the Control Menu is set to Standard method.

Sets the desired battery test depth-of-discharge to a value between 0 and 100%.

Make sure that the set time duration is shorter than the max back up time of your

battery bank. Otherwise, you will drain the battery and trigger a fault – Batt Volt Low.

The default value is set to 20% DoD.

AUTO TEST

Automatic Test

Available when

CHARGER on the Control Menu is set to Standard method.

If the GUI periodic self test is enabled, this starts the test when it is scheduled to

take place.

SHUTDOWN

Shutdown AC

and DC (On/

Off)

When this function is switched

On, the Alpha FXM inverter is shut off. Neither Line

nor Inverter power is supplied to the load. If a dry contact was used as a LVD, the

LVD will open.

SHUTDOWN AC

Shutdown AC

(On/Off)

When this function is switched

On, the Alpha FXM inverter is shut off. Neither Line

nor Inverter power is supplied to the load.

SHUTDOWN DC

Shutdown DC

(On/Off)

When this function is switched

On, the LVD configured relay will be de-energized.  

Applies when ANY programmable dry contact is programmed to be the Low Voltage

Disconnect indicator. See "UPS Maintenance > Relay & Load Shed" on page 41.

When the function is switched from

On to Off, a 10 second delay occurs before the

LVD configured relay is re-energized.