10 connecting the voltage supply, 1 diq/s 182 xt-4-pr (line power version), 10 connecting the voltage supply -35 – YSI DIQ/S 182 XT-4-PR User Manual
Page 49: 1 diq/s 182 xt-4-pr (line power version) -35
System 182 XT-4
Installation
3 - 35
ba76027e01
02/2012
3.10
Connecting the voltage supply
Note
The following two paragraphs describe how to connect both models of
the DIQ/S 182 XT-4-PR to the voltage supply. How to connect
additional power supply modules is described in the operating manual
of the respective power supply module.
3.10.1 DIQ/S 182 XT-4-PR (line power version)
Warning
If the power supply is incorrectly connected, it may represent a
danger to life from electric shock. Pay attention to the following
points during installation:
The DIQ/S 182 XT-4-PR must only be connected by a qualified
electrician.
The DIQ/S 182 XT-4-PR must only be connected in a voltage-
free condition.
The power supply must fulfill the specifications given on the
nameplate and in chapter 10 T
A switch or circuit breaker must be provided in the building
installation as an interrupt facility for the DIQ/S 182 XT-4-PR.
The interrupt facility must be
– installed in the vicinity of the DIQ/S 182 XT-4-PR, easily
accessible by the user and
– marked as an interrupt facility for the DIQ/S 182 XT-4-PR.
After it has been installed, the DIQ/S 182 XT-4-PR may only be
opened if the mains voltage has been switched off beforehand.
Materials required
Wire end sleeves, suitable for the power line, with suitable crimping
tool
1 x cable gland, matched to the cable diameter (see section 3.9 on
Tools
Cable stripping knife
Wire stripper
Phillips screwdriver
Small screwdriver.
Preparing the power
cable
1
Cut off the cable to the required length.
2
Strip the cable insulation for approx. 45 mm.