beautypg.com

2 system monitoring, Syst, See section 6.4.2 – YSI DIQ/S 182 XT-4-PR User Manual

Page 105

background image

System 182 XT-4

Relay outputs

6 - 15

ba76027e01

02/2012

6.4.2

System monitoring

Function

The System monitoring enables the monitoring of system errors.

To set up the System monitoring function for a relay output, you have
to select the System option when linking the relay output (see section
6.2.1
).

It can be used to monitor the following system errors:

Settings

Collective error

message

In the case of a Collective error message, the relay opens if one of the
following malfunctions occurs:

 One of the sensors properly registered at the controller does not

supply a valid main measured value

 One of the sensors properly registered at the controller does not

supply a valid secondary measured value

In any case, the relay remains open for 10 seconds and only closes
when the malfunction is no longer present.

In the following cases, the relay does not open despite an invalid
measured value:

 The sensor is being calibrated

 The sensor is in the maintenance condition

 The sensor is being cleaned with the aid of a valve module in the

system (compressed air operated cleaning system).

Settings

Selection

Explanations

Power failure

On
Off

The Power failure On function
monitors the supply voltage in
the
DIQ/S 182 XT-4-PR. If the
voltage falls below a critical
value, the relay switches.

Collective error

On
Off

The Collective errorOnfunction
simultaneously monitors the
proper function of all sensors.
(for details, see below this
table)

Action

Open

For all functions of the System
monitoring
, the relay action is
set to Open.