Display fault messages, Ev charging station, User manual & installation instructions – GE Industrial Solutions NEMA EVSE CHARGING STATION User Manual
Page 55
![background image](/manuals/295741/55/background.png)
g
EV Charging Station
User Manual & Installation Instructions
GE EV Charging Station User Manual
55 of 86
(This picture depicts an example of all CLOSED dip switch positions. For correct settings, refer to below
tables)
The default settings per SKU are given in below table:
1
2
3
4
5
6
7
8
Factory
setting
Factory
setting
Factory
setting
Factory
setting
reserved Language settings Config.
server
CLOSED CLOSED CLOSED OPEN
CLOSED OPEN *) OPEN *) CLOSE **)
*) Language Settings
6 position
7 position
No Display or Set Language Via Config. Server
Close
Close
Spanish
Close
Open
French
Open
Close
English
Open
Open
**) Configuration Server
CLOSE = Normal operation
OPEN = Configuration server
3.5.2 Display fault messages
EVSE controller is capable of providing a full range of Fault troubleshooting options. When the
controller experiences a fault it will display the brief fault description message as well as the specific
fault code on the display.
Fault codes:
0x00000001
Fault indicating that the unit has experienced a ground fault and is waiting the required amount of
time (15 minutes) before it attempts to reclose the main contactor, clear the fault and continue
charging.
0x00000002
Fault indicating that the controller has experienced the maximum allowed number of ground faults
for a charge cycle.. To reset this fault simply disconnect the EVSE plug from the vehicle, and wait for at
least 30 seconds.
Pushed down on “number”
side is the CLOSED position
Figure 55: Dip Switch Settings