Car2512te front-end, Preliminary data sheet, Input: 90v – GE Industrial Solutions CAR2512TE Front-End User Manual
Page 2: Output: 12 v, Standby @ 15w, Absolute maximum ratings, Electrical specifications
GE
Preliminary Data Sheet
CAR2512TE Front-End
Input: 90V
AC
to 264V
AC
; Output: 12 V
DC
@ 2500W; 3.3/5V
DC
standby @ 15W
February 7, 2014
©2013 General Electric Company. All rights reserved.
Page 2
Absolute Maximum Ratings
Stresses in excess of the absolute maximum ratings can cause permanent damage to the device. These are absolute stress ratings only, functional
operation of the device is not implied at these or any other conditions in excess of those given in the operations sections of the data sheet.
Exposure to absolute maximum ratings for extended periods can adversely affect the device reliability.
Parameter
Symbol
Min
Max
Unit
Input Voltage: Continuous
V
IN
0
264
V
AC
Operating Ambient Temperature
T
A
-10
70
1
°C
Storage Temperature
T
STG
-40 85 °C
I/O Isolation voltage to Frame (100% factory Hi-Pot tested)
2121
V
DC
Electrical Specifications
Unless otherwise indicated, specifications apply over all operating input voltage, load, and temperature conditions.
INPUT
Parameter
Symbol
Min
Typ
Max
Unit
Operational Range
V
IN
90 115/230 264 V
AC
Frequency Range (ETSI 300-132-1 recommendation)
F
IN
47 50/60 63 Hz
Main Output Turn_OFF
V
IN
80
V
AC
Maximum Input Current (V
OUT
= V
O, set
, I
OUT
=I
O, max
) V
IN
= 100V
AC
I
IN
14
16
A
AC
V
IN
= 180V
AC
Cold Start Inrush Current
I
IN
40
A
PEAK
(Excluding x-caps, 25C, <10ms, per ETSI 300-132)
Efficiency (T
AMB
=25C, V
IN
= HL, V
O
= 12V
DC
),
100% load
115V / 230V
89 / 91
89 / 94
80 / 90
%
50% load
20% load
Power Factor (V
IN
=230V
AC
, I
OUT
=I
O, max
) PF
0.99
Holdup time
2
(V
OUT
= 12V
DC
, Tamb 25C, I
OUT
=I
O, max
) V
in
= 230V
AC
V
in
= 100V
AC
T 12
15
ms
Early warning prior to output falling below 10.8Vdc (DC_OK signal
goes LO)
2
ms
Ride through
T
10
ms
Leakage Current (V
IN
= 250V
AC
, Fin = 60Hz)
I
IN
3
mA
Isolation Input/Output
3000
V
AC
Input/Frame
1500
V
AC
Output/Frame
100
V
DC
12V
dc
MAIN OUTPUT
Parameter
Symbol
Min
Typ
Max
Unit
Output Power HL / LL [180 – 264 / 90-132 V
AC
] V
DC
≥ 12V
DC
W
0 -
2500/1200
W
V
DC
= 10.8V
DC
0
-
2246/1078
W
Set point
V
OUT
11.9 12.00 12.1 V
DC
Overall regulation (load, temperature, aging)
-3
+3
%
Ripple and noise
3
120
mV
P-P
Turn-ON overshoot
+3
%
Turn-ON delay
T
2
3
sec
1
Derated above 50C at 2.5%/C
2
12V output can decay down to 10.8V
3
Measured across a 10µf tantalum and a 0.1µf ceramic capacitors in parallel. 20MHz bandwidth