GE Industrial Solutions CAR2512TE Front-End User Manual
Car2512te front-end, Preliminary data sheet, Input: 90v
![background image](/manuals/295537/1/background.png)
GE
Preliminary Data Sheet
February 7, 2014
©2013 General Electric Company. All rights reserved.
CAR2512TE Front-End
Input: 90V
AC
to 264V
AC
; Output: 12V
DC
@ 2500W; 3.3/5V
DC
standby @ 15W
Features
Efficiency meets 80plus ‘Platinum’ requirements
Universal input with PFC
Constant power characteristic
2 front panel LEDs: 1-input;2-[DC_OK, fault, warning]
Remote ON/OFF control of the 12Vdc output
Remote sense on the 12Vdc output
No minimum load requirements
Active load sharing (single wire)
Hot Plug-ability
Standby orderable either as 3.3Vdc or 5Vdc
Auto recoverable OC & OT protection
Operating temperature: -10 - 70C (de-rated above 50C)
Digital status & control: I
2
C and PMBus serial bus
EN/IEC/UL60950-1 2
nd
edition; UL, CSA, VDE , and CCC
EMI: class A FCC docket 20780 part 15, EN55022
Meets EN61000 immunity and transient standards
Shock & vibration: Meets IPC 9592 Class II standards
Applications
12Vdc distributed power architectures
Datacom and Telecom applications
Mid to high-end Servers
Routers/Switches
Broadband Switches
ATE Equipment
Description
The CAR2512TE Front-End provides highly efficient isolated power from worldwide input mains in a compact 1U
industry standard form factor in an unprecedented power density of 25W/in
3
. Ideal for applications where mid to light
load efficiency is of key importance. This front-end is complemented by the CAR2512DC dc/dc converter designed to
convert 48/60Vdc power of telecom central offices. This plug and play approach offers rapid system reconfiguration
by simply replacing the power supply.
The high-density, front-to-back airflow is designed for minimal space utilization and is highly expandable for future
growth. The industry standard PMBus compliant I
2
C communications buss offers a full range of control and
monitoring capabilities. The SMBAlert signal pin alerts customers automatically of any state change within the power
supply.
*
UL is a registered trademark of Underwriters Laboratories, Inc.
†
CSA is a registered trademark of Canadian Standards Association.
‡
VDE is a trademark of Verband Deutscher Elektrotechniker e.V.
§
Intended for integration into end-user equipment. All the required procedures for CE marking of end-user equipment should be followed. (The CE mark is placed on selected products.)
** ISO is a registered trademark of the International Organization of Standards.
+ PMBus name and logo are registered trademarks of the System Management Interface Forum (SMIF)