Par. o-56 preset reference select, 56 preset reference select, Af-600fp bacnet – GE Industrial Solutions AF-600 FP BACnet User Manual
Page 39
NB!
This parameter is active only when par. O-01 Control Site is set to [0] Digital and control word.
O-55 Set-up Select
Option:
Function:
Select control of the drive set-up selection via the terminals (digital input) and/or via the network.
[0]
Digit Input
Activates the set-up selection via a digital input.
[1]
Bus
Activates the set-up selection via the serial communication port or network option module.
[2]
Logic AND
Activates the set-up selection via the network/serial communication port, AND additionally via one of the
digital inputs.
[3] *
Logic OR
Activate the set-up selection via the network/serial communication port OR via one of the digital inputs.
NB!
This parameter is active only when par. O-01 Control Site is set to [0] Digital and control word.
O-56 Preset Reference Select
Option:
Function:
Select control of the drive Preset Reference selection via the terminals (digital input) and/or via the net-
work.
[0]
Digit Input
Activates Preset Reference selection via a digital input.
[1]
Bus
Activates Preset Reference selection via the serial communication port or network option module.
[2]
Logic AND
Activates Preset Reference selection via the network/serial communication port, AND additionally via one
of the digital inputs.
[3] *
Logic OR
Activates the Preset Reference selection via the network/serial communication port OR via one of the
digital inputs.
NB!
This parameter is active only when par. O-01 Control Site is set to [0] Digital and control word.
BN-70 BACnet Device Instance
Range:
Function:
1*
[0 - 4194304]
Enter a unique ID number for the BACnet device.
NB!
This parameter is active only when par. O-30 Protocol is set to [9] Drive Option.
BN-72 MS/TP Max Masters
Range:
Function:
127*
[0 - 127]
Define the address of the master which holds the highest address in this network. Decreasing this value
optimises polling for the token.
NB!
This parameter is active only when par. O-30 Protocol is set to [9] Drive Option.
BN-73 MS/TP Max Info Frames
Range:
Function:
1*
[1 - 65534]
Define how many info/data frames the device is allowed to send while holding the token.
AF-600FP BACnet
38
6