This parameter is active only when par. O-01 Control Site is set to [0] Digital and control word.

O-55 Set-up Select

Option:

Function:

Select control of the drive set-up selection via the terminals (digital input) and/or via the network.

[0]

Digit Input

Activates the set-up selection via a digital input.

[1]

Bus

Activates the set-up selection via the serial communication port or network option module.

[2]

Logic AND

Activates the set-up selection via the network/serial communication port, AND additionally via one of the
digital inputs.

[3] *

Logic OR

Activate the set-up selection via the network/serial communication port OR via one of the digital inputs.

NB!
This parameter is active only when par. O-01 Control Site is set to [0] Digital and control word.

O-56 Preset Reference Select

Option:

Function:

Select control of the drive Preset Reference selection via the terminals (digital input) and/or via the net-
work.

[0]

Digit Input

Activates Preset Reference selection via a digital input.

[1]

Bus

Activates Preset Reference selection via the serial communication port or network option module.

[2]

Logic AND

Activates Preset Reference selection via the network/serial communication port, AND additionally via one
of the digital inputs.

[3] *

Logic OR

Activates the Preset Reference selection via the network/serial communication port OR via one of the
digital inputs.

NB!
This parameter is active only when par. O-01 Control Site is set to [0] Digital and control word.

BN-70 BACnet Device Instance

Range:

Function:

1*

[0 - 4194304]

Enter a unique ID number for the BACnet device.

NB!
This parameter is active only when par. O-30 Protocol is set to [9] Drive Option.

BN-72 MS/TP Max Masters

Range:

Function:

127*

[0 - 127]

Define the address of the master which holds the highest address in this network. Decreasing this value
optimises polling for the token.

NB!
This parameter is active only when par. O-30 Protocol is set to [9] Drive Option.

BN-73 MS/TP Max Info Frames

Range:

Function:

1*

[1 - 65534]

Define how many info/data frames the device is allowed to send while holding the token.