Af-600fp bacnet – GE Industrial Solutions AF-600 FP BACnet User Manual
Page 36
In LonWorks, the time-out function is also activated when the following SNVT's fail to be updated within the time period specified in par. O-03 Control Word Timeout
Time:
nviStartStop
nviReset Fault
nviControlWord
nviDrvSpeedStpt
nviRefPcnt
nviRefHz
O-05 End-of-Timeout Function
Option:
Function:
Select the action after receiving a valid control word following a time-out. This parameter is active only
when par. O-04 Control Word Timeout Function is set to [Set-up 1-4].
[0]
Hold set-up
Retains the set-up selected in par. O-04 Control Word Timeout Function and displays a warning, until par.
O-06 Reset Control Word Timeout toggles. Then the drive resumes its original set-up.
[1] *
Resume set-up
Resumes the set-up active prior to the time-out.
O-06 Reset Control Word Timeout
Option:
Function:
This parameter is active only when the choice Hold set-up [0] has been selected in par. O-05 End-of-
Timeout Function .
[0] *
Do not reset
Retains the set-up specified in par. O-04 Control Word Timeout Function, [Select setup 1-4] following a
control time-out.
[1]
Do reset
Returns the drive to the original set-up following a control word time-out. When the value is set to Do
reset [1], the drive performs the reset and then immediately reverts to the Do not reset [0] setting.
O-07 Diagnosis Trigger
Option:
Function:
This parameter has no function for LonWorks.
[0] *
Disable
[1]
Trigger on alarms
[2]
Trigger alarm/warn.
O-10 Control Word Profile
Option:
Function:
Select the interpretation of the control and status words corresponding to the installed network. Only the
selections valid for the network installed in slot A will be visible in the Keypad display.
[0] *
Drive Profile
[1]
PROFIdrive profile
[5]
ODVA
[7]
CANopen DSP 402
O-30 Protocol
Option:
Function:
Protocol selection for the integrated Drive (standard) Port (RS485) on the control card.
Parameter group BN-7# is only visible when Drive Option [9] is chosen.
[0] *
Drive
Communication according to the Drive Protocol as described in the AF-600 FP Design Guide, RS-485
Installation and Set-up.
[1]
Drive MC
Same as Drive [0] but to be used when downloading SW to the drive or uploading dll file (covering infor-
mation regarding parameters available in the drive and their inter-dependencies) to Drive Control Tool
DCT10.
[2]
Modbus RTU
Communication according to the Modbus RTU protocol as described in the AF-600 FP Design Guide,
RS-485 Installation and Set-up.
AF-600FP BACnet
35