Object ID
Object Name
Read/Write
Changeable
Description
Non volatile ram
Store
AF-600 FP Pa-
rameter
Alarm
notifi-
cation
Triggers Bus Time-
out
AV:31
Ext. 2 Setpoint
W/R
No
AF-600 FP
XC-35
No
No
AV:32
Ext. 2 reference [Unit]
W/R
No
AF-600 FP
XC-37
No
No
AV:33
Ext. 2 Feedback [Unit]
W/R
No
AF-600 FP
XC-38
No
No
AV:34
Ext. 2 Proportional Gain
W/R
No
AF-600 FP
XC-41
No
No
AV:35
Ext. 2 Integral Time (Sec)
W/R
No
AF-600 FP
XC-42
No
No
AV:36
Ext. 2 Differential Time
W/R
No
AF-600 FP
XC-43
No
No
AV:37
Ext. 2 Dif. Gain
W/R
No
AF-600 FP
XC-44
No
No
AV:38
Ext. 3 Setpoint
W/R
No
AF-600 FP
XC-55
No
No
AV:39
Ext. 3 Reference [Unit]
W/R
No
AF-600 FP
XC-57
No
No
AV:40
Ext. 3 Feedback [Unit]
W/R
No
AF-600 FP
XC-58
No
No
AV:41
Ext. 3 Proportional Gain
W/R
No
AF-600 FP
XC-61
No
No
AV:42
Ext. 3 Integral Time (Sec)
W/R
No
AF-600 FP
XC-62
No
No
AV:43
Ext. 3 Differential Time
(Sec)
W/R
No
AF-600 FP
XC-63
No
No
AV:44
Ext. 3 Dif. Gain Limit
W/R
No
AF-600 FP
XC-64
No
No
Table 5.1: Analog values cont.
5.2.2 Binary Input- and Output Objects
Object Id
Object Name
Read/Write
Changeable De-
scription
Non volatile
ram Store
Drive Par.
Alarm
notifi-
cation
Triggers Bus
Timeout
BI:0
Digital input 33
Read
No
No
DR-60/00
No
No
BI:1
Digital input 32
Read
No
No
DR-60/01
No
No
BI:2
Digital input 29
Read
No
No
DR-60/02
No
No
BI:3
Digital input 27
Read
No
No
DR-60/03
No
No
BI:4
Digital input 19
Read
No
No
DR-60/04
No
No
BI:5
Digital input 18
Read
No
No
DR-60/05
No
No
BI:6
Digital input 37
Read
No
No
DR-60/06
No
No
BI:7
Digital input X30/2
Read
No
No
DR-60/07
No
No
BI:8
Digital input X30/3
Read
No
No
DR-60/08
No
No
BI:9
Digital input X30/4
Read
No
No
DR-60/09
No
No
BI:10
Digital input DR-60/10*
Read
No
No
DR-60/10
No
No
BI:11
Digital input DR-60/11*
Read
No
No
DR-60/11
No
No
BI:12
Digital input DR-60/12*
Read
No
No
DR-60/12
No
No
BI:13
Digital input DR-60/13*
Read
No
No
DR-60/13
No
No
BI:14
Digital input DR-60/14*
Read
No
No
DR-60/14
No
No
BI:15
Digital input DR-60/15*
Read
No
No
DR-60/15
No
No
Table 5.1: Binary inputs
Bl:7 - Bl:19 values are only available if the option is installed.
*) Reserved for future options!
AF-600FP BACnet