Af-600fp bacnet – GE Industrial Solutions AF-600 FP BACnet User Manual
Page 22
Object ID
Object Name
Read/Write
Changeable
Description
Non volatile ram
Store
AF-600 FPPa-
rameter
Alarm
notifi-
cation
Triggers Bus Time-
out
AV:0
Reference
W/R
Yes
No
MRV
No
Yes
AV:1
Speed Act. Value
W/R
Yes
No
MAV
Yes
Yes
AV:2
Bus Feedback1
W/R
Yes
No
O-94
No
Yes
AV:3
Bus Feedback2
W/R
Yes
No
O-95
No
Yes
AV:4
Bus Feedback3
W/R
Yes
No
O-96
No
Yes
AV:5
Motor Voltage
Read
Yes
No
DR-12
Yes
No
AV:6
Motor Current
Read
Yes
No
DR-14
Yes
No
AV:7
Motor Torque %
Read
Yes
No
DR-22
Yes
No
AV:8
DC Link Voltage
Read
Yes
No
DR-30
Yes
No
AV:9
Motor thermal
Read
Yes
No
DR-18
Yes
No
AV:10
Heat sink Temperature
Read
Yes
No
DR-12
Yes
No
AV:11
Inverter Thermal
Read
Yes
No
DR-35
Yes
No
AV:12
Operating Hours
Read
No
No
ID-00
No
No
AV:13
Running Hours
Read
No
No
ID-01
No
No
AV:14
KWh Counter
Read
No
No
ID-02
No
No
AV:15
Power [KW]
Read
No
No
DR-10
No
No
AV:16
PID Start Speed [Hz]
W/R
No
AF-600 FP
CL-83
No
No
AV:17
PID Proportional Gain
W/R
No
AF-600 FP
CL-93
No
No
AV:18
PID Integral Time (Sec)
W/R
No
AF-600 FP
CL-94
No
No
AV:19
PID Differential Time (Sec) W/R
No
AF-600 FP
CL-95
No
No
AV:20
PID Dif. Gain Limit
W/R
No
AF-600 FP
CL-96
No
No
AV:21
On Reference Bandwith
W/R
No
AF-600 FP
CL-84
No
No
AV:22
Ext. 1 Setpoint
W/R
No
AF-600 FP
XC-15
No
No
AV:23
Ext. 1 Reference [Unit]
W/R
No
AF-600 FP
XC-17
No
No
AV:24
Ext. 1 Feedback [Unit]
W/R
No
AF-600 FP
XC-18
No
No
AV:25
Ext. 1 Propotional Gain
W/R
No
AF-600 FP
XC-21
No
No
AV:26
Reserved
W/R
No
Na
AV:27
Ext. 1 Integral Time (Sec)
W/R
No
AF-600 FP
XC-22
No
No
AV:28
Ext. 1 Differential Time
(Sec)
W/R
No
AF-600 FP
XC-23
No
No
AV:29
Ext. 1 Dif. Gain Limit
W/R
No
AF-600 FP
XC-24
No
No
AV:30
Reserved
W/R
No
Na
Table 5.1: Analog values
AF-600FP BACnet
21
5