Af-600fp bacnet – GE Industrial Solutions AF-600 FP BACnet User Manual
Page 37
[3]
Metasys N2
Communication according to the Metasys N2 Protocol.
[4]
FLN
[9]
Drive Option
To be used when a gateway is connected to the integrated RS-485 port, e.g. the BACnet gateway. Fol-
lowing changes will take place:
-Address for the Drive port will be set to 1 and par. O-31 Address, is now used to set the address for the
gateway on the network, e.g. BACnet.
-Baud rate for theDrive port will be set to a fixed value (115.200 Baud) and par. O-32 Baud Rate, is now
used to set the baud rate for the network port (e.g. BACnet) on the gateway.
O-31 Address
Range:
Function:
1.*
[1. - 126.]
Enter the address for the Drive (standard) port.
Valid range: 1 - 126.
O-32 Drive Port Baud Rate
Option:
Function:
Baud rate selection depends on Protocol selection in par. O-30 Protocol.
[0]
2400 Baud
[1]
4800 Baud
[2] *
9600 Baud
[3]
19200 Baud
[4]
38400 Baud
[5]
57600 Baud
[6]
76800 Baud
[7]
115200 Baud
Default refers to the Drive Protocol.
O-33 Drive Port Parity
Option:
Function:
Parity and Stop Bits for the protocol par. O-30 Protocol using the Drive Port. For some of the protocols,
not all options will be visible. Default depends on the protocol selected.
[0] *
Even Parity, 1 Stop Bit
[1]
Odd Parity, 1 Stop Bit
[2]
No Parity, 1 Stop Bit
[3]
No Parity, 2 Stop Bits
O-35 Minimum Response Delay
Range:
Function:
10. ms*
[5. - 10000. ms]
Specify the minimum delay time between receiving a request and transmitting a response. This is used
for overcoming modem turnaround delays.
O-36 Maximum Response Delay
Range:
Function:
10001. ms* [11. - 10001. ms]
Specify the maximum permissible delay time between transmitting a request and receiving a response.
Exceeding this delay time will cause control word time-out.
O-37 Maximum Inter-Char Delay
Range:
Function:
25.00 ms*
[0.00 - 35.00 ms]
Specify the maximum permissible time interval between receipt of two bytes. This parameter activates
time-out if transmission is interrupted.
AF-600FP BACnet
36