Sta report status, Error messages, B - 8 – GE Industrial Solutions Galaxy Vector Rack Mounted Controller J85501M-1 User Manual
Page 90: Table b-16: error messages

Galaxy Rack-Mounted Vector Controller J85501M-1
Appendix B - 8 T1.317 Objects and Attributes
Issue 2 January 2008
sta Report Status
Syntax
sta obj,att
where: obj,attr is an object-attribute pair. For example, ps1,sid.
Description:
This command reports the value of the measurement, configuration, or control parameters
in the system. A couple of examples are listed below to illustrate how this command works.
sta dc1,vdc
- report plant voltage
sta dc1,adc
- report plant load current
The command line would respond as follows for first command listed above.
* sta dc1,vdc
:DC1
VDC=-52.48
.
* _
The “*” in the example above is the user command line prompt. The line “:DC1” indicates
that the information that follows is for the plant object. The line starting with “VDC”
identifies the DC voltage. The “.” line is the end-of-command identifier.
Error Messages
While logging into the vector controller or while entering commands you may encounter
one or more of the following error messages:
Table B-16: Error Messages
Error Message
Description
!-112,SYNTAX ERROR
Unrecognizable command was entered.
!-220,SECURITY
Super-user command was entered by a mere user.
!-221,EXCESSIVE LOGIN ATTEMPTS
Too many attempts were made to login with an unrecognized password.
!-223,INVALID PASSWORD
New password contains an illegal character.
!-224,NEW PASSWORD MISMATCH
First and second copy of new passwords don't match
!-304,INVALID PARAMETER
An attempt was made to change a parameter to an illegal value.
!-319,INVALID ATTRIBUTE
An invalid object id was specified in the command or, a command referred to
an attribute that doesn't support it.
!-320,INVALID OBJECT
An invalid object id was specified in the command