GE Industrial Solutions Galaxy Vector Rack Mounted Controller J85501M-1 User Manual
Page 30

Galaxy Rack-Mounted Vector Controller J85501M-1
3 - 2 Operation
Issue 2 January 2008
BD threshold default is set at 25.54V standard in 24V systems,
and 51.1V in 48V systems with slope thermal compensation
disabled. In systems with slope thermal compensation, the BD
threshold should be 0.5V below the slope upper temperature
voltage for 24V systems, and 1.0V below the slope upper
temperature voltage for 48V systems. The slope upper
temperature equals:
Float Set Point - (number of cells) · E · (F-D)
See Figure 3-1 for system settings E, F, and D
These levels generally avoid nuisance alarms from transient
conditions yet provide alarm indications early in a true BD
event, so that sufficient time is provided for maintenance
personnel to respond before battery reserve is exhausted. VLV
should be activated towards the end of the battery reserve
voltage to indicate a critical service condition.
Table 3-A: Alarm Identification Standard Assignments
Alarm Description
Alarm Status
Front Panel LED
GCM Relay
No active alarms present
Norm
Green
None
Very low voltage
Major
Red
None
Battery on discharge
Major
Red
BD
High float voltage
Minor
Yellow
None
Very high voltage
Major
Red
HV
Voltage sense fuse alarm
Major
Red
None
AC fail
Minor
Yellow
ACF
Multiple AC fail
Major
Red
ACF
Rectifier fail
Minor
Yellow
None
Multiple rectifier fail
Major
Red
None
Rectifier ID conflict
Major
Red
None
Rectifier manual off alarm
Minor
Yellow
None
Rectifier AC phase alarm
Minor
Yellow
None
Converter fail
Minor
Yellow
None
Multiple converter fail
Major
Red
None
Converter ID conflict
Minor
Yellow
None
Converter distribution alarm
Major
Red
MJF
Converter fan fail minor
Minor
Yellow
None
Converter fan fail major
Major
Red
None
Fuse alarm major
Major
Red
MJF
Auxiliary input major
Major
Red
None
Load Share imbalance
Minor
Yellow
None
Contactor 1 open
Major
Red
None
Contactor 1 failed
Major
Red
None
Contactor 2 open
Major
Red
None
Contactor 2 failed
Major
Red
None
High battery temperature
Major
Red
None
Temperature probe failure
Minor
Yellow
None
Maintenance open alarm
Major
Red
None