Table 4-a: configuration parameters – GE Industrial Solutions Galaxy Vector Rack Mounted Controller J85501M-1 User Manual
Page 52

Galaxy Rack-Mounted Vector Controller J85501M-1
4 - 6 Installation and Configuration
Issue 2 January 2008
the default screen, press MENU twice. If no key is pressed for
approximately three minutes, the display will return to the
default front panel screen.
Refer to Table 4-A as each of the Configuration Parameters is
explained in the following sections. Each section also explains
how to access the data available from these features.
Table 4-A: Configuration Parameters
Main Menu
Heading
Parameter
Description
Range
(24V, 48V Systems)
Default (24V, 48V Systems)
Standard
Custom
Float Voltage
System float
voltage set point
22-28V, 44-56V
27.24V, 54.48V
27.24V, 54.48V
High float voltage
major alarm
25-30V, 50-60V
28.24V, 57V
28.5V, 57.0V
High float voltage
minor alarm
25-30V, 50-60V
27.74V, 56V
27.74, 56.0V
Battery discharge
major alarm
23-27.5V, 46-55V
25.54V, 51.1V
25.0V, 51.1V
Very low voltage
major alarm
20-25.5V, 40-51V
23.00V, 46.00V
23.0V, 46.0V
Rectifiers
Rectifier output
float current limit
30-110%
100%
110%
Number of
rectifiers on line
1-24
24, 1
24
Shunts
System shunt type
Battery, load, none
Battery
Battery
Shunt 1 current
rating
0-9999A
800A
1000A
Shunt 2 current
rating
0-9999A
0A
0A