Galaxy Rack-Mounted Vector Controller J85501M-1
2 - 10 Product Description
Issue 2 January 2008
LVD1, LVD2
Relay contact outputs for LVD contactor control. Contacts are
rated for 10 amps. Power must be provided externally to the
contactor coil. The contactor coil should have battery
permanently attached. The LVD1 and LVD2 contacts should
complete the circuit to DG. This power is switched by the LVD
control contact closure provided.
Table 2-F: LVD Drive Terminals
Contactor
Name
Alarm Board
Description
LVD1
LVD1-CON1
LVD1-CON2
TB3.6
TB3.7
Dry closure provided. External
power required.
LVD2
LVD2-CON1
LVD2-CON2
TB3.11
TB3.12
Office Alarm Relay
Outputs
All alarm output relays are isolated Form C or transfer type
contacts, consisting of Open (O) and Closed (C) contacts, with a
common Return (R(C)) contact. The de-energized state of the
controller forces these contacts to the alarm state. An alarm
condition results in a closure of the Closed contact to the Return
contact, and an open between the Open and Return contacts.
Table 2-G: BLJ3 Office Alarm Relay Output Terminals
Terminal
Alarm
Alarm Description
C
1
R(C)
1
O
1
ACF
Single AC Fail
TB8.1
TB8.2
TB8.3
BD
Battery on Discharge
TB8.9
TB8.10
TB8.11
HV/2ACF/VLV
2
High Voltage / Multiple
AC Fail / Very Low
Voltage
TB8.5
TB8.6
TB8.7
MJF
Major Fuse
TB7.9
TB7.10
TB7.11
PMJ
Power Major
TB7.1
TB7.2
TB7.3
PMN
Power Minor
TB7.5
TB7.6
TB7.7
1. C: Open contacts. Closed to R(C) when alarm condition exists.
R(C): Return (common)
O: Closed contacts. Open to R(C) when alarm condition exists.
2. Relay assignment is determined by the settings of S1.2 and S1.5:
HV alarm
S1.2-0, S1.5=0
2ACF alarm S1.2=1, S1.5=0
VLV alarm
S1.2=0, S1.5=1
Setting both switches to 1 results in activating HV. The S1.2 setting is only read during
GCM power up.
Auxiliary Battery
Supply (ABS)
Auxiliary Battery Supply (ABS) is connected to the battery
discharge bus and fused through F1 (1-1/3A) for user application
on TB4 pins 1, 3, 5, 9, and 11, and TB5 pin 1. F1 is field
replaceable.