Troubleshooting
61
GF Defeat Button is grayed out
Ground Fault protection is disabled
in all the circuit breakers.
Depending on the type of system
purchased, GF may be enabled in
the HMI under User Settings or it
may need to be optioned in the
Compartment ID Button. Contact GE
for details.
OverCurrent Test
Pre-Defined Overcurrent Test-
Short Time
/Instantaneous/Ground Fault
feature grayed out in Test
Selection in pre-defined tests
Protection elements not optioned
and/or enabled for the circuit
breaker selected.
Verify that the Protection enabled
for that circuit breaker in system
based on Table 1-4.
Incorrect Switchgear Configuration
used?
Check if settings downloaded were
same as in HMI.
Observed trip time reads zero
Test cable not connected to either
the test kit or the EntelliGuard
Messenger.
Verify the test kit connector is
attached to the desired circuit
breaker.
User-Defined Mode—Trip module
displays as No trip
Verify that the fault current entered
is greater than any of the LT/ST/IOC
Pickups.
User-Defined
Overcurrent—% Test Results
button grayed out
Test has not been run yet.
Test was aborted.
Pre-Defined Overcurrent
Protection—Test Summary is
grayed out
Test has not been run yet.
Test was aborted.
Automatic Trip Time
Curve—Ground Fault curve
feature grayed out in select curve
type
Ground fault is not enabled for the
selected circuit breaker.
% Error is displayed as 100
Verify that the System Test Kit cable
is connected to the selected circuit
breaker on which the test is
performed and that observed trip
time is not zero.
% Error is displayed as ___
Verify that the point tested is IOC
trip and that trip time is less than
50/60 ms.
Table 1-20 Troubleshooting
Error
Potential Cause
Suggested Fix