1 overcurrent protection test, 1 functions – GE Industrial Solutions Entellisys System Test Kit User Manual
Page 21

System Test Kit
22
1.6.1 Overcurrent Protection Test
1.6.1.1 Functions
Tests various Overcurrent Protection functions. The functions must be optioned and enabled in 
the system to perform the respective tests. 
Long Time (LT) Overcurrent Protection
Verifies the long time overcurrent protection function for a circuit breaker in the system. It can 
be performed as either a trip or no trip test. To test LT, the test kit injects a sum-of-squares 
current value for any phase above the LT pickup setting. The result of the test is a trip time with 
an accuracy of 10% of the expected trip time. 
Short Time (ST) Overcurrent Protection
Verifies the short time overcurrent protection function for a circuit breaker in the system. The 
test can be performed as either a trip or no trip test. To test ST, the test kit injects a 
sum-of-squares current value for any phase above the ST pickup setting. The result of the test is 
a trip time with an accuracy of 10% of the expected trip time.
Instantaneous (IOC) Overcurrent Protection
Verifies the instantaneous overcurrent protection function for a circuit breaker in the system. 
The test can be performed as either a trip or no trip test. To test IOC, the test kit provides an 
input current that exceeds the programmed IOC threshold. The result of the test is a trip time 
with an accuracy of 10% of the expected trip time.
Ground Fault (GF) Protection
Verifies Ground Fault protection function for a circuit breaker in the system. The test can be 
performed as either a trip or no trip test.
In a three-wire system, the test kit will provide three phase currents with vector sum greater 
than the pickup threshold. 
In a four-wire, WYE-system, the test kit will provide three phase currents and a neutral with 
vector sum greater than the pickup threshold. 
In either case, the result is a trip time with an accuracy of 10% of the expected trip time.