PowerWalker WinPower Software V.4.3.0.1 Manual User Manual
Page 34

34
System
selected, System will be
suspended to disk in
shutdown sequence. This
function only can be carry
out in some Windows
platforms and hibernate
support must be enabled
from /Control Panel/Power
Options/Hibernate .
Multi-UPS
input
__
__
__
NO
When the check box is
selected, system won't be
shut down until all the
conditions of all selected
UPS are met.
System
shutdown
need time
Minute
99
1
2
The time to be needed to
shut down the system,
which is from the beginning
of shutting down to the end
of that.
Remote
Shutdown
by Agent
__
__
__
No
If Yes, System will be shut
down by specified Agent.
XX min
shutdown
system
Minute
4320
0
0
Receiving the specified
agent's shutdown signal,
delay XX minutes. System
will be shut down.
Run
Command
File before
Shutdown
__
__
__
Nothing
Before system shutting
down, Agent can execute a
file, if this parameter isn’t
null, Agent will not begin to
shut down the system until
the "Execution file before
system shutting down"
ends.
Shutdown
File Max
Execution
Time
Minute
60
1
1
Before system shutting
down, the time to be
needed to execute the
shutdown file.
Begin
Shutting
down
immediately
while battery
low
__
__
__
Yes
When this check box is
selected and battery low
event occurs, Agent will
shut down the UPS
immediately, otherwise the
shutting down time will be
controlled by battery backup
time.
Shutdown
remote
Agents'
Conditions
__
__
__
__
The condition can be "UPS
be shutdown" or "The time
on battery exceeds setting
time".
Agents be
Shutdown
__
__
__
__
When shutdown condition is
satisfied, Agent will send
shutdown signal to the
appointed remote Agents.
Shutdown
Alarm
Interval
Minute
60
1
1
The interval that Agent pop
up an alarm message
before shutting down.
Start
Warning
before
Minute
60
1
10
If user has setup schedule
shutting down, AGENT will
sound alarm prior to the set