B&B Electronics RT3G-300_310_320_330_340-W - User Manual User Manual
Page 33

B&B Electronics, Inc.
SPECTRE User Manual
33
SPECTRE_User_Manual_2912m
www.bb-elec.com
www.bb-europe.com
bit 8
– Binary output OUT1
bit 9
– Automatic feeder control
bit 10
– Full duplex counter CNT1/CNT2
0x0004
R/-
Maximum log entries in buffer
0x0005
R/W
Marker of log launching and alarms work
0x0006
R/W
Upper 16 bits of current time in seconds, numbered from 1/1/1970
0x0007
R/W
Lower 16 bits of current time in seconds, numbered from 1/1/1970
0x0008
R/W
Upper 16 bits of log entry timestamp
0x0009
R/W
Lower 16 bits of log entry timestamp
0x000A
R/-
Alarm actual status
0x0100
R/-
Binary input status
0x0200
R/W
Binary output status
0x0300
R/-
Recalculate value of analog input AN1 (with sign)
0x0400
R/-
Recalculate value of analog input AN2 (with sign)
0x0500
R/W
Upper 16 bits of counter CNT1 value
0x0501
R/W
Lower 16 bits of counter CNT1 value
0x0502
R/-
Prompt frequency CNT1
0x0503
R/-
Average frequency CNT1
0x0504
R/-
Minimum frequency CNT1
0x0505
R/-
Maximum frequency CNT1
0x0601
R/W
Upper 16 bits of counter CNT2 value
0x0601
R/W
Lower 16 bits of counter CNT2 value
0x0602
R/-
Prompt frequency CNT2
0x0603
R/-
Average frequency CNT2
0x0604
R/-
Minimum frequency CNT2
0x0605
R/-
Maximum frequency CNT2
0x0F00
R/-
0x0000 always
0x0F01
R/-
0x0000 always
0x0F02
R/-
Upper 16 bits of seconds, number from 1.1.1970
0x0F03
R/-
Lower 16 bits of seconds, number from 1.1.1970
0x0F04
R/-
Alarms status
bit 0
– active level on input BIN1
bit 1
– active level on input BIN2
bit 2
– active level on input BIN3
bit 3
– active level on input BIN4
bit 4
– analog input lower limit overrun AN1