5. Assembly
58
PNEG-720-G2 12" and 16" Series II Sweep
Press OK.
REL1 should be displayed on the unit.
Press
or
on the display unit until SET is shown (not SKIP or OFF).
Press OK.
SETP should be displayed on the unit.
Press
or
on the display unit the 90% of FLA value is shown.
Press OK.
ACT1 should be displayed on the unit.
Press
or
on the display unit until INCR is shown (not DECR).
Press OK.
HYS1 should be displayed on the unit.
For this control panel hysteresis (HYS1) is measured as the different between 90% of full load amps and
110% of no load amps.
90% of full load amps: ____ minus 110% of no load amps: ____
Press
or
on the display unit until the correct value is shown.
Press OK.
ERR1 should be displayed on the unit.
Press
or
on the display unit until DEAC is shown (not HOLD, ACTI or NONE).
Press OK.
ON.DE should be displayed on the unit.
Press
or
on the display unit until 0 is shown.
Press OK.
OF.DE should be displayed on the unit.
Press
or
o the display unit until 20 is shown.
Press OK.
REL2 should be displayed on the unit.
Press
or
on the display unit until OFF is shown (not SET or SKIP).
Press OK.
E.PAS should be displayed on the unit.
Press
or
on the display unit until NO is shown.
Press OK.