beautypg.com

R 6.3.1), Wha-gw, Operation – VEGA WHA-GW-WIRELESSHART GATEWAY User Manual

Page 75: 1 reset, 2 self test

background image

WHA-GW-*

Operation

22

1981

2011

-0

7

75

6.3.1

Reset

Figure 6.9Additional Functions > Reset

Additional Functions > Reset

6.3.2

Self Test

After pressing the Perform Self-Test button in the Additional Functions > Self Test

menu the device carries out a self test.

The results of the self test can be seen in the Diagnosis menu (see chapter 6.2).

Parameter

Description

Device Reset

Press this button to restart the Gateway software application without
any impact on the established network (which is not reformed).
This function does not set the parameters of the WHA-GW back to
their default values. It only restarts the Gateway software.

Rebuild
Instrument
List

Press this button to generate the Instrument List (see chapter 5.4.2,
see chapter 6.3.5) from scratch.
The existing Instrument List is overwritten. Note that the Modbus
addresses of the devices in the network will be changed by resetting
the Instrument List!
It is recommended to create a backup of the existing Instrument List
first (see chapter 6.3.5).

Reform
Network

Press this button to restart and reestablish the network. For example,
this function is needed to activate a new Network ID (see chapter
5.4.1). Depending on the size of the network, this process may take
several minutes.
This function does not set the parameters of the WHA-GW back to
their default values. It only restarts the network.