Wha-gw, Commissioning, 3 adding device dtm – VEGA WHA-GW-WIRELESSHART GATEWAY User Manual
Page 43: Adding the device dtm

WHA-GW-*
Commissioning
22
1981
2011
-0
7
43
4.6.3
Adding Device DTM
Adding the Device DTM
1. In the project view, right-click on the entry of the communication DTM you have added in
the previous step.
2. To add the device DTM, choose Add device.
The Device for window opens (see on page 43).
Device for window with Gateway DTM
3. Select the entry WHA-GW.
HART IP communication DTM parameters
Corresponding Gateway parameters
Parameter
Explanation
Default
Parameter
Default
Tag
Gateway name in the
Project view of
PACTware. Any name
may be entered (not
relevant for
connection to
gateway)
WHA-GW
–
–
Bus
Address
Gateway polling
address; must match
the settings of the
Gateway.
1
Parameterization
> Wired Communication
> Protocols > HART
> Bus Address
1
UDP
Address
IP address of the
Gateway; must match
the settings of the
Gateway.
192.168.1.1
Parameterization
> Wired Communication
> Interfaces > Ethernet
> IP Address
192.168.1.1
UDP Port
Gateway port number
(HART over UDP);
must match the
settings of the
Gateway.
5094
Parameterization
> Wired Communication
> Protocols > HART
> Port Number
5094