VEGA VEGAPULS 45 VBUS User Manual
Page 85
VEGAPULS 42, 44 and 45 – VBUS
85
Technical data
Ambient conditions
Vessel pressure
-1 … 16 bar (-100 … 1600 kPa)
-1 … 40 bar (-100 … 4000 kPa)
Ambient temperature on the housing
-30 °C … +80 °C
Process temperature (flange temp.)
-20 °C … +150 °C (option -40 °C … +150 °C)
Storage and transport temperature
-60 °C … +80 °C
Protection
IP 66 and IP 67
Protection class
II
Overvoltage category
III
Ex technical data
Comprehensive data in the attached approval documents (yellow binder)
Intrinsically safe version
- classification ia
intrinsically safe in conjunction with a separator
or safety barrier
- classification mark
II 2G EEx ia II T6
- Ex approved
Zone 1 (ATEX)
Zone 1 (CENELEC, PTB, IEC)
or
- classification mark
II 1G EEx ia IIC T6
- Ex approved
Zone 0, Zone 1 (ATEX)
Zone 0, Zone 1 (CENELEC, PTB, IEC)
Permissible ambient temperature
on the housing
- T6
-40 °C … +55 °C
- T5
-40 °C … +70 °C
- T4, T3
-40 °C … +85 °C
- T2, T1
-40 °C … +70 °C
Permissible ambient temperature on the
antenna system if used in Ex areas
- T6
-40 °C … +85 °C
- T5
-40 °C … +100 °C
- T4
-40 °C … +135 °C
- T3
-40 °C … +150 °C
1)
Similar to DIN 16 086, reference conditions acc. to IEC 770, e.g.
temperature 15 °C … 35 °C; humidity 45 % … 75 %; air pressure 860 mbar … 1060 mbar
2)
The adjustment time (also called actuating time, response time or adjustment period) is the time required by
the sensor to output the correct level (with max. 10% deviation) after a sudden level change.
3)
Average emitted power (electromagnetic energy) per cm² received on an object directly in front of the
antenna. The received emitted power depends on the antenna version and the distance.