Electrical connection

15 sensors via one two-wire cable on the VEGALOG 571 processing system

• 15 sensors with power supply and digital output signals via one two-wire cable on one input

card of the VEGALOG 571 processing system.

• Display of measured values integrated in the sensor.
• Optional external indicating instrument (can be mounted up to 25 m away from the sensor

also in Ex area).

• Adjustment with PC or adjustment module MINICOM (can be plugged into the sensor or into

the external indicating instrument VEGADIS 50).

• Max. resistance of the signal cable with 15 sensors on one two-wire cable 10

per wire

(instead of 15

Ω),

max. 1000 m cable length.

1)

Sensor wiring should be looped in screened
cables. Please make sure that no earth
compensation currents flow via the screens.
You avoid earth compensation currents (when
grounding at both ends) by connecting the cable
screen on one end (e.g. in the switching cabinet)
via a capacitor (e.g. 10 nF; 1500 V) with the
ground potential.

Processings see also Product
Information "Signal conditio-
ning instruments series 500"

Current outputs

Voltage output

Relay outputs

Transistor output

Fault signals

Display outputs

Digital wiring
Connection to all
bus systems

Screened cable in case of electromag-
netic interferences

1)

VEGALOG 571 processing system
with input cards in 19" rack. 15
sensors on one module card and
cable

Interface cable RS 232

15 sensors per two-wire cable
individual grouping