7 technical data, 1 data – VEGA VEGAPULS 45 VBUS User Manual
Page 83
VEGAPULS 42, 44 and 45 – VBUS
83
1)
Min. distance of the antenna to the medium 5 cm
7 Technical data
7.1 Data
Power supply
Supply voltage
The sensor is powered by the VEGAMET signal
conditioning instrument, the VEGALOG proces-
sing system or the VEGATRENN 548V Ex
separator
Number of sensors per two-wire cable
VEGAMET max. 2 sensors
VEGALOG max. 15 sensors (recommended 5)
VEGATRENN (Ex) max. 5 sensors
Sensor voltage
min. 12 V, max. 36 V DC (Ex: max. 29 V DC)
Current consumption
max. 6 mA
Power consumption
max. 81 mW
Resistance of the signal cable
max. 15
Ω
per wire
Cable length
- 1.5 mm
2
and 2.5 mm
2
max. 1000 m
- 1 mm
2
max. 840 m
- 0.75 mm
2
max. 630 m
Measuring range
1)
VEGAPULS 42
- standard ø 40 mm horn
0 … 10 m
- optional
ø 48 mm horn
0 … 15 m
ø 75, 95 mm horn
0 … 20 m
VEGAPULS 44
- DN 50, ANSI 2"
0 … 15 m
- DN 80, 100, ANSI 3", 4", 6"
0 … 20 m
VEGAPULS 45
0 … 4 m
Output signal
Signal output
digital VBUS output signal in two-wire technology
(VEGA-Bus).
the digital output signal (meas. signal) is
modulated to the power supply and further
processed in the signal conditioning instrument
or in the processing system.
Integration time (adjustable)
- in the sensor
0 … 999 seconds
- in the signal conditioning instrument
0 … 600 seconds
Load
resistance of the signal cable max. 15 Ohm per
wire and max. 1000 m cable length
(with 15 sensors on one two-wire cable
max. 10 Ohm per wire)
Technical data