7 technical data, 1 data – VEGA VEGAPULS 45 VBUS User Manual

Page 83

background image

VEGAPULS 42, 44 and 45 – VBUS

83

1)

Min. distance of the antenna to the medium 5 cm

7 Technical data

7.1 Data

Power supply

Supply voltage

The sensor is powered by the VEGAMET signal
conditioning instrument, the VEGALOG proces-
sing system or the VEGATRENN 548V Ex
separator

Number of sensors per two-wire cable

VEGAMET max. 2 sensors
VEGALOG max. 15 sensors (recommended 5)
VEGATRENN (Ex) max. 5 sensors

Sensor voltage

min. 12 V, max. 36 V DC (Ex: max. 29 V DC)

Current consumption

max. 6 mA

Power consumption

max. 81 mW

Resistance of the signal cable

max. 15

per wire

Cable length

- 1.5 mm

2

and 2.5 mm

2

max. 1000 m

- 1 mm

2

max. 840 m

- 0.75 mm

2

max. 630 m

Measuring range

1)

VEGAPULS 42

- standard ø 40 mm horn

0 … 10 m

- optional

ø 48 mm horn

0 … 15 m

ø 75, 95 mm horn

0 … 20 m

VEGAPULS 44

- DN 50, ANSI 2"

0 … 15 m

- DN 80, 100, ANSI 3", 4", 6"

0 … 20 m

VEGAPULS 45

0 … 4 m

Output signal

Signal output

digital VBUS output signal in two-wire technology
(VEGA-Bus).
the digital output signal (meas. signal) is
modulated to the power supply and further
processed in the signal conditioning instrument
or in the processing system.

Integration time (adjustable)

- in the sensor

0 … 999 seconds

- in the signal conditioning instrument

0 … 600 seconds

Load

resistance of the signal cable max. 15 Ohm per
wire and max. 1000 m cable length
(with 15 sensors on one two-wire cable
max. 10 Ohm per wire)

Technical data