Installation guide – Veris Industries H8036 SERIES Install User Manual
Page 9

Z201686-0N
PAGE 9
©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]
08122
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
TM
H8035/H8036
INSTALLATION GUIDE
As an alternative to the table on the previous page, invert the values for use as divisors, in which the integer value returned by the Enercept is divided by a number from the
table below. In most cases, the divisors are a more compact number.
Addr
Units
100A
300/400A
800A
1600A
2400A
40001
kWh
128
32
16
8
4
40002
kWh
1.9531E-3
4.8828E-4
2.4414E-4
1.2207E-4
6.1035E-5
40003
kW
250
62.5
31.25
15.625
7.8125
40004
kVAR
250
62.5
31.25
15.625
7.8125
40005
kVA
250
62.5
31.25
15.625
7.8125
40006
---
32768
40007
Volts
32
40008
Volts
64
40009
Amps
256
64
32
16
8
40010
kW
1000
250
125
62.5
31.25
40011
kW
1000
250
125
62.5
31.25
40012
kW
1000
250
125
62.5
31.25
40013
---
32768
40014
---
32768
40015
---
32768
40016
Volts
32
40017
Volts
32
40018
Volts
32
40019
Volts
64
40020
Volts
64
40021
Volts
64
40022
Amps
256
64
32
16
8
40023
Amps
256
64
32
16
8
40024
Amps
256
64
32
16
8
40025
kW
250
62.5
31.25
15.625
7.8125
40026
kW
250
62.5
31.25
15.625
7.8125
40027
kW
250
62.5
31.25
15.625
7.8125