INSTALLATION GUIDE

As an alternative to the table on the previous page, invert the values for use as divisors, in which the integer value returned by the Enercept is divided by a number from the
table below. In most cases, the divisors are a more compact number.

Addr

Units

100A

300/400A

800A

1600A

2400A

40001

kWh

128

32

16

8

4

40002

kWh

1.9531E-3

4.8828E-4

2.4414E-4

1.2207E-4

6.1035E-5

40003

kW

250

62.5

31.25

15.625

7.8125

40004

kVAR

250

62.5

31.25

15.625

7.8125

40005

kVA

250

62.5

31.25

15.625

7.8125

40006

---

32768

40007

Volts

32

40008

Volts

64

40009

Amps

256

64

32

16

8

40010

kW

1000

250

125

62.5

31.25

40011

kW

1000

250

125

62.5

31.25

40012

kW

1000

250

125

62.5

31.25

40013

---

32768

40014

---

32768

40015

---

32768

40016

Volts

32

40017

Volts

32

40018

Volts

32

40019

Volts

64

40020

Volts

64

40021

Volts

64

40022

Amps

256

64

32

16

8

40023

Amps

256

64

32

16

8

40024

Amps

256

64

32

16

8

40025

kW

250

62.5

31.25

15.625

7.8125

40026

kW

250

62.5

31.25

15.625

7.8125

40027

kW

250

62.5

31.25

15.625

7.8125