INSTALLATION GUIDE
USING INTEGER DATA TYPES
Unlike the floating-point data type, the integer data type can only represent whole numbers between zero and 65535. To convert a data point value into the number it
represents, multiply the value by a constant, as indicated in the table below.
Some data points require different multipliers for each amperage range, while others (e.g. volts and power factor) use the same multiplier regardless of the amperage range of
the product. The latter are indicated by single row values.
Addr
Units
100A
300/400A
800A
1600A
2400A
40001
kWh
7.81E-03
0.03125
0.0625
0.125
0.25
40002
kWh
512
2048
4096
8192
16384
40003
kW
0.004
0.016
0.032
0.064
0.128
40004
kVAR
0.004
0.016
0.032
0.064
0.128
40005
kVAR
0.004
0.016
0.032
0.064
0.128
40006
---
3.0518E-5
40007
Volts
0.03125
40008
Volts
0.015625
40009
Amps
3.906E-03
0.015625
0.03125
0.0625
0.1250
40010
kW
0.001
0.004
0.008
0.016
0.032
40011
kW
0.001
0.004
0.008
0.016
0.032
40012
kW
0.001
0.004
0.008
0.016
0.032
40013
---
3.0518E-5
40014
---
3.0518E-5
40015
---
3.0518E-5
40016
Volts
0.03125
40017
Volts
0.03125
40018
Volts
0.03125
40019
Volts
0.015625
40020
Volts
0.015625
40021
Volts
0.015625
40022
Amps
3.906E-03
0.015625
0.03125
0.0625
0.1250
40023
Amps
3.906E-03
0.015625
0.03125
0.0625
0.1250
40024
Amps
3.906E-03
0.015625
0.03125
0.0625
0.1250
40025
kW
0.004
0.016
0.032
0.064
0.128
40026
kW
0.004
0.016
0.032
0.064
0.128
40027
kW
0.004
0.016
0.032
0.064
0.128