H8035/H8036

INSTALLATION GUIDE

USING INTEGER DATA TYPES

Unlike the floating-point data type, the integer data type can only represent whole numbers between zero and 65535. To convert a data point value into the number it
represents, multiply the value by a constant, as indicated in the table below.

Some data points require different multipliers for each amperage range, while others (e.g. volts and power factor) use the same multiplier regardless of the amperage range of
the product. The latter are indicated by single row values.

Addr

Units

100A

300/400A

800A

1600A

2400A

40001

kWh

7.81E-03

0.03125

0.0625

0.125

0.25

40002

kWh

512

2048

4096

8192

16384

40003

kW

0.004

0.016

0.032

0.064

0.128

40004

kVAR

0.004

0.016

0.032

0.064

0.128

40005

kVAR

0.004

0.016

0.032

0.064

0.128

40006

---

3.0518E-5

40007

Volts

0.03125

40008

Volts

0.015625

40009

Amps

3.906E-03

0.015625

0.03125

0.0625

0.1250

40010

kW

0.001

0.004

0.008

0.016

0.032

40011

kW

0.001

0.004

0.008

0.016

0.032

40012

kW

0.001

0.004

0.008

0.016

0.032

40013

---

3.0518E-5

40014

---

3.0518E-5

40015

---

3.0518E-5

40016

Volts

0.03125

40017

Volts

0.03125

40018

Volts

0.03125

40019

Volts

0.015625

40020

Volts

0.015625

40021

Volts

0.015625

40022

Amps

3.906E-03

0.015625

0.03125

0.0625

0.1250

40023

Amps

3.906E-03

0.015625

0.03125

0.0625

0.1250

40024

Amps

3.906E-03

0.015625

0.03125

0.0625

0.1250

40025

kW

0.004

0.016

0.032

0.064

0.128

40026

kW

0.004

0.016

0.032

0.064

0.128

40027

kW

0.004

0.016

0.032

0.064

0.128