GOLD CGi Gas-Fired Water Boiler — Boiler Manual

Prepare boiler location — air contamination

Table 1 Corrosive or destructive contaminants and likely locations

1d

Please review the following information on potential
combustion air contamination problems.

Refer to

Table 1

for products and areas which may cause

contaminated combustion air.

CONSTRUCTION DUST HAZARD

— Airborne particulates, such as drywall dust

or fiberglass dust, will cause blockage of the CGi burners, resulting in carbon monoxide

production, a fire hazard, or building freeze damage. If the boiler is operated during

construction, you must isolate the boiler to provide clean air for combustion.

If you are

unable to ensure uncontaminated air in the boiler vicinity at all times, you must

inspect the boiler at least once weekly

. When inspecting, clean the burners if necessary

using the procedure given on page 45. Failure to follow these guidelines could result in

severe personal injury, death or substantial property damage.

Products to avoid

Areas likely to have contaminants

Spray cans containing chloro/fluorocarbons

Dry cleaning/laundry areas and establishments

Permanent wave solutions

Swimming pools

Chlorinated waxes/cleaners

Metal fabrication plants

Chlorine-based swimming pool chemicals

Beauty shops

Calcium chloride used for thawing

Refrigeration repair shops

Sodium chloride used for water softening

Photo processing plants

Refrigerant leaks

Auto body shops

Paint or varnish removers

Plastic manufacturing plants

Hydrochloric acid/muriatic acid

Furniture refinishing areas and establishments

Cements and glues

New building construction

Antistatic fabric softeners used in clothes dryers

Remodeling areas

Chlorine-type bleaches, detergents, and cleaning
solvents found in household laundry rooms

Garages with workshops

Adhesives used to fasten building products and
other similar products

Buildings under construction (where air is
contaminated with particulates)

Airborne particulates (drywall dust, fiberglass
particles, road or gravel dust, lint, etc.)

To prevent potential of severe personal injury or death, check for products or areas listed

below before installing boiler. If any of these contaminants are found:
• remove contaminants permanently

— OR —

• isolate boiler and provide outside combustion air. See national, provincial or local codes

for further information.