GOLD CGi Gas-Fired Water Boiler — Boiler Manual

Figure 29 Typical main burner flame

Check burner flames

View pilot and main flames through the inspection port

in the base burner shield.

Pilot burner flame

(

Figure 28

)

PROPER pilot flame characteristics

1. Blue flame.
. Inner cone engulfing pilot flame sensor.
3. Pilot flame sensor glowing cherry red.

IMPROPER pilot flame characteristics

1. Overfired — Large flame lifting or blowing

past pilot flame sensor.

. Underfired — Small flame. Inner cone not

engulfing pilot flame sensor.

3. Lack of primary air — Yellow flame tip.
4. Incorrectly heated pilot flame sensor.

Main burner flame

(

Figure 29

)

PROPER main burner flame characteristics

1. Yellow-orange streaks may appear (caused by

dust).

IMPROPER main burner flame characteristics

1. Overfired — Large flames.
. Underfired — Small flames.
3. Lack of primary air — Yellow tipping on

flames (sooting will occur).

Figure 28 Typical pilot burner flame

Start-up — operate boiler

(continued)

7b

Start-up — if boiler doesn’t start . . .

7c

4. Gas not turned on at meter or boiler?

5. Incoming gas pressure less than:

5” w.c. for natural gas? 11” w.c. for propane gas?

6. If none of the above corrects the problem, refer to

Troubleshoot-

ing

,

section

11

of this manual.

1. Loose connections, blown fuse or

service switch off?

. High limit switch set below boiler

water temperature?

3. Thermostat set below room tempera-

ture?

Check for: