Field wiring

6

Thermostat

1. Connect thermostat as shown on wiring diagram

on boiler.

.

Install on inside wall away from influences of

drafts, hot or cold water pipes, lighting fixtures,

television, sunrays, or fireplaces.

3. If thermostat has a heat anticipator, set heat antici-

pator in thermostat to match power requirements

of equipment connected to it. If connected directly

to boiler, set for 0.1 amps plus gas valve current.

See information on wiring diagram as shown in

Figure 32

, page 39. For other devices, refer to

manufacturer’s specifications. Wiring diagram on

boiler gives setting for control module and gas valve.

Also see instructions with thermostat.

Junction Box (furnished)

1. Connect 10 VAC power wiring as shown in

Figure 27

.

. Fused disconnect or service switch (15 amp. recom-

mended) may be mounted on this box. For those

installations with local codes which prohibit installa-

tion of fused disconnect or service switch on boiler,

install a x 4 cover plate on the boiler junction box

and mount the service switch remotely as required

by the code.

For your safety,

turn off electrical power supply at

service entrance panel before making any electrical

connections

to avoid possible electric shock hazard.

Failure to do so can cause severe personal injury or

death.

Wiring must be N.E.C. Class 1.

If original rollout thermal fuse element wire as supplied

with boiler must be replaced, use only type

200°C

wire

or equivalent. If other original wiring as supplied with

boiler must be replaced, type

105°C

wire or equivalent

must be used.

Boiler must be

electrically grounded

as required by

National Electrical Code ANSI/NFPA 0–latest edi-

tion.

Electrical installation must

comply with:

1. National Electrical Code and any other national,

state, provincial or local codes or regulations.

. In Canada, CSA C.1 Canadian Electrical Code

Part 1, and any local codes.

Wiring connections

Boiler is shipped with controls completely wired.

Figure 27

Field wiring connections —

service switch and thermostat

(or end switch)

provided by installer

The CGi control module is polarity-sensitive. The hot and neutral wires must be connected to

the correct leads. A flashing POWER light usually indicates reversed polarity of 10 VAC lead

wires.