Water piping — multiple zones, Gold cgi gas-fired water boiler — boiler manual – Weil-McLain GOLD CGI 550-110-710/0107 User Manual

Page 23

background image

Part Number 550-110-710/0107

3

GOLD CGi Gas-Fired Water Boiler — Boiler Manual

Figure 18

Zoning with circulators

— return water 130°F or higher.

Figure 19

Zoning with zone valves

— return water 130°F or higher.

1

Boiler isolation (balancing) valves

2

Flow/check valve

3

System or zone circulator

5

Zone valve

6

Drain valve

9

Relief valve

10

Automatic air vent (with diaphragm-type expansion tank), or con-

nect to tank fitting (closed-type expansion tank).

DO NOT

use an

automatic air vent when using closed-type expansion tank. It would

allow air to leave the system, causing waterlogging of the expansion

tank.

11

Fill valve

12

Diaphragm-type or bladder-type expansion tank, if used (For

closed-type expansion tank, pipe from top of air separator to tank

fitting as in

Figure 17

.)

13

Air separator and automatic vent, if used (Note that the fill valve

must always be connected to the expansion tank, regardless of loca-

For systems with possible low return-water temperature (such as converted gravity systems,

radiant heating systems and heat pump systems), refer to the special piping suggestions of

Figures 20 – 24

, as applies. Failure to prevent sustained low return water temperature to

the boiler could cause corrosion of the boiler sections, resulting in severe personal injury,

death or substantial property damage.

Water piping — multiple zones

(continued)

4c