Water piping — single-zone system, Gold cgi gas-fired water boiler — boiler manual, Diaphragm-type or bladder- type expansion tank – Weil-McLain GOLD CGI 550-110-710/0107 User Manual
Page 21: Closed-type expansion tank
Part Number 550-110-710/0107
1
GOLD CGi Gas-Fired Water Boiler — Boiler Manual
Water piping — single-zone system
4b
Diaphragm-type or bladder-
type expansion tank
(Figure 16)
1. Ensure expansion tank size will handle boiler and
system water volume and temperature. Tank must
be located in boiler return piping as close to boiler
as possible, before inlet side of circulator. See tank
manufacturer’s instructions for details.
. Install an
automatic air vent
as shown.
Figure 16
Diaphragm- or bladder-type expansion
tank — Piping to single-zone system
using diaphragm-type or bladder-type
expansion tank. See Table 6 for piping
sizes.
Figure 17
Closed-type expansion tank — Piping
to single-zone system using closed-
type expansion tank. See Table 6 for
piping sizes.
Closed-type expansion tank
(Figure 17)
1. Ensure expansion tank size will handle boiler and
system water volume and temperature. See tank
manufacturer’s instructions for details.
. Connect tank to ½” NPT tapping located behind
supply outlet, using ½” NPT piping. Pitch any
horizontal piping up towards tank 1 inch per 5 feet
of piping.
Use
Figure 16
or
Figure 17
only for single-zone systems designed for return water at least 130°F.
For systems with low return water temperature possible, such as converted gravity systems
and radiant heating systems, refer to the special piping suggestions of pages 4-9. Failure to
prevent low return water temperature to the boiler could cause corrosion of the boiler sections
or burners, resulting in severe personal injury, death or substantial property damage.
Undersized expansion tanks cause system water to be lost from relief valve and makeup water
to be added through fill valve. Eventual section failure can result.