GOLD CGi Gas-Fired Water Boiler — Boiler Manual

30

Part Number 550-110-710/0107

Gas piping

5

Table 7 Pipe capacity for 0.60 specific gravity natural gas

Natural Gas:

1. Refer to

Table 7

for pipe length and diameter. Base

on rated boiler input (divide by 1,000 to obtain cubic
feet per hour).

Table 7

is only for gas with

specific

gravity 0.60, with a pressure drop through the
gas piping of 0.30” w.c.

For additional gas pipe

sizing information, refer to ANSI Z3.1 (or B149.1
or B149. for Canadian installations).

. Inlet pressure required at gas valve inlet:

• Maximum: 13” w.c.
• Minimum: 5” w.c.
• Manifold gas pressure: 3.5” w.c.

3. Install 100% lockup gas pressure regulator in supply

line

if inlet pressure exceeds 13” w.c.

Adjust for

13” w.c. maximum.

Propane Gas:

1. Contact gas supplier to size pipes, tanks and 100%

lockup gas pressure regulator.

. Adjust propane supply regulator provided by gas

supplier for 13” w.c. maximum pressure.

3. Inlet pressure required at gas valve inlet:

• Maximum: 13” w.c.
• Minimum: 11” w.c.
• Manifold gas pressure: 10” w.c.

Connecting gas supply piping to boiler

1. Remove jacket front panel and refer to

Figure 26

to pipe gas to boiler.

a.

Install drip leg

at inlet of gas connection to boiler. Where local

utility requires drip leg to be extended to the floor, use appropri-

ate length of pipe between cap and tee.

b.

Install ground joint union

for servicing, when required.

c.

Install manual shutoff valve

in gas supply piping outside boiler

jacket when required by local codes or utility requirements.

d.

In Canada

— When using manual main shutoff valve, it

must be

identified

by the installer.

.

Support piping

with hangers, not by boiler or its accessories.

3.

Purge all air

from gas supply piping.

4. Before placing boiler in operation,

check boiler and its gas connection

for leaks

.

a.

Close manual main shutoff valve

during any pressure testing at

less than 13” w.c.

b.

Disconnect boiler and gas valve from gas supply piping

dur-

ing any pressure testing greater than 13” w.c.

Do not check for gas leaks with an open flame

— use bubble test. Failure to use bubble test or check

for gas leaks can cause severe personal injury, death or

substantial property damage.

5.

Use pipe dope compatible with propane gases.

Apply sparingly

only to male threads of pipe joints so that pipe dope does not block gas

flow.

Failure to apply pipe dope

as detailed above can result

in severe personal injury, death or substantial property

damage.

Figure 26 Gas supply piping