Part Number 550-110-710/0107

5

GOLD CGi Gas-Fired Water Boiler — Boiler Manual

Please read before proceeding

Failure to adhere to the guidelines on this page can result in severe personal injury, death

or substantial property damage.

• Continual fresh makeup water will reduce

boiler life. Mineral buildup in sections re-

duces heat transfer, overheats cast iron, and

causes section failure. Addition of oxygen

and other gases can cause internal corrosion.

Leaks in boiler or piping must be repaired

at once to prevent makeup water.

• Do not add cold water to hot boiler. Thermal

shock can cause sections to crack.

Glycol — potential fire hazard —

All glycol is flammable when exposed to high

temperatures. If glycol is allowed to accumulate

in or around the boiler or any other potential

ignition source, a fire can develop. In order to

prevent potential severe personal injury, death

or substantial property damage from fire and/or

structural damage:
• Never store glycol of any kind near the boiler

or any potential ignition source.

• Monitor and inspect the system and boiler

regularly for leakage. Repair any leaks im-

mediately to prevent possible accumulation

of glycol.

• Never use automotive antifreeze or ethylene

glycol in the system. Using these glycols can

lead to hazardous leakage of glycol in the

boiler system.

When servicing boiler —

• To avoid electric shock, disconnect electrical supply

before performing maintenance.

• To avoid severe burns, allow boiler to cool before

performing maintenance.

Boiler operation —

• Do not block flow of combustion or ventilation air to

boiler.

• Should overheating occur or gas supply fail to shut

off, do not turn off or disconnect electrical supply to

circulator. Instead, shut off the gas supply at a location

external to the appliance.

• Do not use this boiler if any part has been under

water. Immediately call a qualified service technician

to inspect the boiler and to replace any part of the

control system and any gas control that has been under

water.

Boiler water —

• Do not use petroleum-based cleaning or sealing

compounds in boiler system. Water seal deterioration

will occur, causing leakage between sections. This can

result in substantial property damage.

• Do not use “homemade cures” or “boiler patent

medicines”. Serious damage to boiler, personnel and/or

property may result.

Installer

Read all instructions before in-

stalling

. Follow all instructions in

proper order to prevent personal

injury or death.

• Consider

piping and installation

when determining

boiler location.

• Any

claims for damage or shortage in shipment

must be filed immediately against the transportation
company by the consignee.

User

This manual is for use only by your qualified
heating installer/service technician.

• Please refer to the

User’s Information Manual

for

your reference.

• We recommend regular

service by a qualified

service technician, at least annually

.

When calling or writing about the boiler— Please have the boiler model number from the
boiler rating label and the CP number from the boiler jacket. You may list the CP number in
the space provided on the

Installation and service certificate

found on page 36.

The boiler contains ceramic fiber and fiberglass materials. Use care when handling these

materials per instructions on page 68 of this manual. Failure to comply could result in severe

personal injury.