Page 47: Review with owner

background image

Part Number 550-110-710/0107

4

GOLD CGi Gas-Fired Water Boiler — Boiler Manual

Review with owner

1. Review the

User’s Information Manual

with the

owner.

. Emphasize the need to perform the maintenance

schedule specified in the

User’s Information

Manual

(and in this manual as well).

3. Remind the owner of the need to call in a licensed

contractor should the boiler or system exhibit any

unusual behavior.

4. Remind the owner to follow the proper shutdown

procedure and to schedule an annual start-up at the
beginning of the next heating season.

Cleaning boiler

heating surfaces

The boiler contains ceramic fiber
and fiberglass materials. Use care
when handling these materials per
instructions on

page 68

of this

manual. Failure to comply could
result in severe personal injury.

1. Shut down boiler:

• Follow “

To Turn Off Gas to Appliance

” instructions

on boiler and

Operating instructions

.

• Do not drain boiler unless it will be exposed to

freezing temperatures. If using antifreeze in sys-
tem, do not drain.

. Follow shutdown procedure.
3. Remove venting system connection to boiler.
4. Remove top jacket panel. Turn back insulation.
5. Remove collector box/transition assembly. Clean sealant

from assembly and sections.

6. Remove radiation plates hanging between sections.
. Remove burners from base. Brush and vacuum burners

to remove all dust and lint. Verify that all burner ports are
free of debris.

8. Place newspapers in base of boiler to collect soot.
9. Clean between sections with wire flue brush.
10. Remove newspaper and soot. Vacuum or brush base and

surrounding area.

11. Reinstall radiation plates.
1. Replace collector box/transition assembly. Seal with seal-

ant. Obtain gas-tight seal to prevent flue gas spillage and
carbon monoxide emissions, resulting in severe personal
injury or death.

13. Replace insulation and jacket top panel.
14. Start up boiler following Section

7

, pages 3-35 of this

manual and the boiler

Operating instructions

. Excessive

sooting indicates improper gas combustion. If found
check for proper combustion and make any necessary
adjustments.

Safety relief valves should be

reinspected AT LEAST

ONCE EVERY THREE YEARS

, by a licensed plumb-

ing contractor or authorized inspection agency, to

ensure that the product has not been affected by

corrosive water conditions and to ensure that the

valve and discharge line have not been altered or

tampered with illegally. Certain naturally occurring

conditions may corrode the valve or its compo-

nents over time, rendering the valve inoperative.

Such conditions are not detectable unless the valve

and its components are physically removed and

inspected. This inspection must only be conducted

by a plumbing contractor or authorized inspection

agency — not by the owner. Failure to reinspect the

boiler relief valve as directed could result in unsafe

pressure buildup, which can result in severe personal

injury, death or substantial property damage.

Following installation, the

valve lever must be

operated AT LEAST ONCE A YEAR

to ensure that

waterways are clear. Certain naturally occurring

mineral deposits may adhere to the valve, rendering

it inoperative. When manually operating the lever,

water will discharge and precautions must be taken

to avoid contact with hot water and to avoid water

damage. Before operating lever, check to see that a

discharge line is connected to this valve directing

the flow of hot water from the valve to a proper

place of disposal otherwise severe personal injury

may result.

If no water flows, valve is inoperative.

Shut down boiler until a new relief valve has been

installed.

Boiler relief valve

1. Inspect the relief valve and lift the lever to verify flow as in the

following warnings, excerpted from a relief valve manufacturer’s

warning label. Before operating any relief valve, ensure that it is

piped with its discharge in a safe area to avoid severe scald potential.

Read manual Section

4

before proceeding further.

. After following the above warning directions, if the relief valve

weeps or will not seat properly, replace the relief valve. Ensure that

the reason for relief valve weeping is the valve and not over-pres-

surization of the system due to expansion tank waterlogging or

undersizing.

Figure 35 Relief valve, typical

10b

Service & maintenance – annual start-up

(cont.)